Analog inputs, Connecting a potentiometer to analog input 1, Connecting a motion controller to the analog input – Applied Motion SV7-C-CE User Manual
Page 34: 34 sv7 hardware manual, In/out1

34
SV7 Hardware Manual
920-0012F
12/18/2014
Connecting a Potentiometer to Analog Input 1
Connecting a Motion Controller to the Analog Input
Analog Inputs
The SV drives feature two analog inputs. Each input can
accept a signal range of 0 to 5 VDC, ±5 VDC, 0 to 10
VDC or ±10 VDC. The drive can be configured to oper-
ate in torque, speed or position modes. Input impedance
of each analog input is 10K ohms to GND.
Note: The analog inputs and the communications
circuitry are referenced to GND only. Therefore a con-
nection must be made to the SV7 GND to complete the signal path.
Use
QuickTuner™ to set the signal function, range, offset, deadband and filter frequency. Please see
the
QuickTuner™ manual or consult the software help for more information.
inside drive
AIN1
AIN2
GND
1
2
13
DB-25 Connector
Signal
Conditioning
Signal
Conditioning
1-10k
Ω
pot
cw
ccw
IN/OUT1
GND
AIN1
+5V OUT
18
1
AIN2
2
13
signal (from motion controller)
signal return
IN/OUT1
GND
AIN1
1
AIN2
2
13