6.2 Local Control

The Control Panel includes a red Local/Stop/Remote selector switch (padlockable in all three positions;
a ¼" (6 mm) hasp is recommended) and a black Open/Close rotary switch (spring-return to center). The
Open and Close switches may be configured to allow either push-to-run (inching) control or maintained
control.

Local Indication

The Control Panel includes the following:

• 32-character graphical LCD

Displays valve position as “PERCENT OPEN” and the current actuator status.

• Red/Green LED Indicators – the color assignment for the red and green LEDs is reversible as

standard.

Red ON = Valve fully open

Red “BLINKING” = Valve opening

Green “BLINKING” = Valve closing

Green ON = Valve fully closed

• Yellow LED

Yellow ON = Actuator available for remote operation,

= Valve stopped in Intermediate position.

Yellow “BLINKING” = Monitor Relay de-energized, actuator not available for remote operation.

6.3 Remote Control Modes of Operation

The actuator may be controlled remotely by two, three or four wires.

• Four-Wire Control – Three momentary contacts. Valve can be opened, closed or stopped.
• Two-Wire Control – Single open or closed contact. Valve can be opened or closed, but not stopped in

mid-travel.

• Three-Wire Maintained – Two momentary contacts for self-maintained control. Valve can be opened

or closed but not stopped in mid-travel.

• Three-Wire Inching – Two “push-to-run” contacts. Valve can be opened, closed and stopped in

mid-travel.

Refer to Figure 15.4 for remote wiring connections.

Advertising