16.3 Network Wiring – Profibus DP and PA

Please refer to LMENIM2336 for detailed installation instructions.

Profibus is based on RS 485 communication. The standard EN 50170 specifies the cable for use with
Profibus DP and PA. Table 16.1 shows specifications that need to be fulfilled by the Profibus cable.

Table 16.1 – Specifications for the Profibus Cable

Parameter

Type – Profibus DP

Impedance

135 to 165 ohm/3 to 20 MHz

Capacity

< 30 pF/m

Resistance

< 110 ohm/km

Wire gauge

> 0.64 mm

Conductor area

> 0.34 mm

2

The Profibus DP cable is a shielded twisted pair cable.

In general, there are two different types of cables available. The most commonly used cable has
solid wire for the Profibus line.

When there is a need for more flexiblity (bending) and higher environmental resistance, a cable with
stranded wire for the Profibus line and special jackets shall be used.

Limitorque recommends the use of:

• Belden 3079A Specifications, 22 AWG, shielded, solid two conductor

Key Specifications

• Capacitance/ft = 8.5 pF
• Nominal Impedance (ohms) – 150.0

Network Wiring – Profibus PA – Belden 3076F

Please refer to IEC 61158 and ANSI/ISA S.50.02 Part 2-1992 for network wiring guidelines.

Maximum number of devices on a segment = 32 (including repeaters)

Table 16.2 – Maximum Segment Length

Data transfer

rate in kbit/s

9.6

19.2

45.45

93.75

187.5

500

1500

3000

6000

12000

Maximum

segment

length in m

1200

1200

1200

1200

1000

400

200

100

100

100