Table 16.3 – Belden Cable Specifications

Belden

Part No.

AWG

(Stranding)

dia. Inches

Nom. DCR

Insulation

material

(color code)

Nominal

O.D.

Nom

Impedance

(ohms)

Nominal

Capacitance

Test

Frequency

(MHz)

Maximum

Attenuation

dB/100ft

3082A

2 – 15 AWG

(19 x 28)

3.6 ohm/1000 ft

11.8 ohm/km

Power pair

(Black/Red)

12.2 mm

120

12.0 pF/ft

0.125

0.5

1

0.13

0.25

1.36

2 – 18 AWG

(19 x 30)

6.9 ohm/1000 ft

22.7 ohm/km

Data pair

(Blue/White)

3084A

2 – 22 AWG

(19 x 34)

17.5 ohm/1000

ft

57.4 ohm/km

Power pair

(Black/Red)

7.2 mm

120

12.0 pF/ft

0.125

0.5

1

0.29

0.50

1.70

2 – 18 AWG

(19 x 36)

28.0 ohm/1000

ft

91.9 ohm/km

Data pair

(Blue/White)

Table 16.4 – Total Cable Length Between Repeaters or Nodes:

Network Size

125 KBPS

250 KBPS

500 KBPS

Thick Trunk Length

500 m (1,640 ft)

250 m (1,640 ft)

100 m (1,640 ft)

Thin Trunk Length

100 m (328 ft)

100 m (328 ft)

100 m (328 ft)

Flat Trunk Length

380 m (1,250 ft)

200 m (656 ft)

75 m (246 ft)

Maximum Drop Length

6 m (20 ft)

6 m (20 ft)

6 m (20 ft)

Cumulative Drop Length

156 m (512 ft)

78 m (256 ft)

39 m (128 ft)

Note: Each actuator includes 0.60 meters of internal drop length.