Limitorque UEX FCD LMENIM1205-03-AQ – 05/15

flowserve.com

Figure 15.4 – Optional Features Wiring Diagrams

EXTERNAL LOAD – APT & ATT

4-20 mA SIGNAL - 470 ohms MAXIMUM for 99.9% accuracy/750 ohms

MAXIMUM for 99% accuracy

0-10 VDC SIGNAL - 2700 ohms MINIMUM for 99% accuracy and 1000

ohms for 99.9% accuracy.

MODUTRONIC

COMMAND SIGNAL = 4-20 mA

INPUT IMPEDANCE = 150 ohms

INPUT CAPACITANCE = 0.1 µF ±30%

NOTE:

ACTUATORS SUPPLIED WITH “R” DEVICES ARE SHIPPED WITH

DEFAULT SETTINGS AS SHOWN ON THE DIAGRAM, UNLESS

OTHERWISE SPECIFIED.

EXACT END POSITION INDICATION

ON TORQUE-SEATED VALVES, THE LCD AND “S” CONTACTS

CONFIGURED AS END-OF-TRAVEL LIMITS AUTOMATICALLY PROVIDE

EXACT END POSITION INDICATION.

ANALOG INPUT

STANDARD SIGNAL 4-20 mA

INPUT IMPEDANCE = 350 ohms

INPUT CAPACITANCE = 0.1 µF ±30%

99% ACCURACY

CONFIGURABLE SCALING

INT ROTORS

LIMIT SWITCHES 9-16 MUST BE WIRED DIRECTLY TO THE LIMIT

SWITCH ASSEMBLY.

CONNECTIONS

CONNECTION LANDED ON INTERFACE BOARD.

MODUTRONIC

STANDARD SIGNAL 4-20mA

20

21

-ve ANALOG INPUT

+ve ANALOG INPUT

47

49

APT

or

ATT

4-20mA OUTPUT

0-10VDC OUTPUT

COMMON -Ve

48

ANALOG POSITION TRANSMITTER

Optional voltages or currents; 0-20 mA, 4-20
mA, 0-10 VDC, 2-10 VDC, 0-5 VDC, 1-5 VDC