Total cable length between repeaters or nodes with repeaters:

• @ 9.6 kbps: 6560 ft (2 km)
• @ 19.2 kbps: 3300 ft. (1 km)
Key Specifications

• Resistance/1000 ft = 24 AWG (7 x 32)

24 ohms each conductor (48 ohms for the pair)

• Capacitance/ft. = 12.8 pF (conductor-to-conductor)
• Capacitance/ft. = 23 pF (conductor-to-shield)

Figure 16.1 – Typical Modbus Network Wiring Diagrams – Single Loop

Legend:

MOV - Motor Operated Valve
A1 -Data Channel 1
A1*-Data Channel 1*
A2 -Data Channel 2
A2*-Data Channel 2*
N/C-No Connection

-Shielded cable

Notes:

Correct polarity for field unit and master station

connections is necessary for proper operation.

The connections shown are typical. The number of

MOVs will vary up to a maximum of 250.

The ground connection should be a ground rod or

ground grid.

41

15

A2

A2*

29

A1

A1*

30

16

Shield

N/C

41

15

A2

A2*

29

A1

A1*

30

16

Shield

N/C

41

15

A2

A2*

29

A1

A1*

30

16

Shield

N/C

MOV-1

MOV-2

MOV-250