Actuator configuration – Flowserve UEX Limitorque User Manual

Page 39

Advertising
background image

39

Limitorque UEX FCD LMENIM1205-03-AQ – 05/15

flowserve.com

14

Actuator Configuration

14.1 Local Configuration

UEX controllers may be configured through the CSE control station switches, with settings visible on the
LCD display. Settings that can be initiated or changed include:

• Direction of rotation
• Action on ESD
• External inhibits
• Remote control operating mode
• Motor thermostat action
• Stop valve on torque or position
• All optional features (Modutronic, Modbus, FF H1, PB-DPV1, PB-PA, DeviceNet, Timers, APT, etc.)

14.2 Default Configuration

Unless otherwise specified, UEX controllers will be shipped with the following configuration, which
becomes effective after the L120 limit switches are properly set.

• Open stop by limit
• Close stop by limit
• Maintained local controls
• Clockwise to close
• ESD is “off” and set to “IGNORE.”
• Inhibits enabled, turned “OFF”
• Remote control – three-wire maintained and Multi-mode
• Password – 100
• Modutronic Option (if installed)