Flowserve ValveSight Diagnostics User Manual

Page 48

Advertising
background image

ValveSight Diagnostics for HART User Manual FCD VSENSF0001-02-AQ 03/15

48

Upper Position Cutoff Setting

The “Upper Position Cutoff Setting” box shows the input command signal above which the positioner applies full force to
open the valve. The default value is 110%.

Lower Position Cutoff Setting

The “Lower Position Cutoff Setting” box shows the input command signal below which the positioner applies full force to
close the valve. The default value is 1%.

Data Management

Select

Apply to save the selections to the positioner. Retrieve can be used to view values currently stored in the posi-

tioner.

12.4 Soft Limits

Soft Limits are software controlled travel stops for the valve assembly. Since they are software controlled, soft limits are
not held in the memory on loss of signal or air because the software is not able to control the valve in these situations. If
soft limits are active, they show as grey areas at either end of travel on the main dashboard view.