Page Line Ground Fault Re-generation

When a ground fault is detected at a remote LE200-RM Line Extender, the ground fault can be duplicated
on the local Page/Party

®

system cable. DIP switch SW5 position 3 enables regeneration of the ground

fault. Refer to Figure 6 for the location of switch SW5 on the Main PCBA and Table 8 below for setting
options.

Table 8. Page Line Ground Fault Regeneration Setting on Main PCBA

SW5-3

Page Line Ground Fault Regeneration

Open*

Disabled - Page line ground faults detected on the remote system cable are NOT
regenerated on the local system cable.

Closed

Enabled - Page line ground faults detected on the remote system cable are regenerated on
the local system cable.

N

OTES

:

1. The ground fault regeneration feature is used in SmartSeries systems to allow a ground fault on the

remote cable segment to be detected by the system control cabinet. Disable this feature if the Line
Extender is not installed in this type system.

2. Changes to this parameter take effect without cycling power.
3. *Indicates default position.

Page Line Ground Fault Output Contact

The Model LE200-RM provides a relay contact that activates whenever a ground fault is detected on the
local page line, remote page line or both the page lines. The ground fault detection feature (described
above) must be enabled. The contact output can be used to activate an external device or system which
annunciates the fault condition. The DIP switch SW5 positions 4 and 5 configure which page line ground
faults activate this contact. Refer to Figure 6 for the location of switch SW5 on the Main PCBA and Table
9 below for setting options.

Table 9. Page Line Ground Fault Contact Setting on Main PCBA

SW5-4

SW5-5

Page Line Ground Fault Contact

Closed

Closed

Disabled

Closed

Open

Remote page line ground fault activates the contact.

Open

Closed

Local page line ground fault activates the contact.

Open*

Open*

Both Local and Remote page line ground faults activate the contact.

N

OTES

: 1. Changes to this parameter take effect without cycling power.

2.

*Indicates

default

position.