12. DO NOT use power line wiring of inadequate capacity. (Use gauge specified by the wiring
diagram or wire chart provided in Section 4).
13. DO NOT use a circuit breaker of improper size. (See Section 4).
14. DO NOT install fill pipe to tank where it can be submerged with standing water.
15. DO NOT use the GASBOY fuel dispensing equipment to remove water ballast from the
storage tank.
16. DO NOT use gaskets on covers of explosion-proof type boxes. The sealing compound found
around wires at various locations within conduit is a requirement of the National Electrical
Code and should not be disturbed. Ensure that the mating surfaces between the junction box
and cover are free of dirt, debris, nicks and scratches. Tighten junction box covers before
replacing panels.
17. DO NOT use knock-out boxes or flexible conduit for installing this unit. All power and lighting
wires should be run in threaded, rigid, metal conduit. All threaded connections must be
drawn up tight with five (5) threads minimum engagement. Only one opening in the AC
junction box is provided with a plug at the factory. At completion of the installation, it is the
installer's responsibility to ensure that any unused openings are plugged.
FOUNDATION
When constructing the island for the dispensing equipment, be sure to extend the island
excavation beyond the depth of the frost line. Leave open an area from the inside edge of the
unit's base as shown on the specific base layout. Unless required by local regulations, do not
cement the pipes and conduits into the island. The open area within the base will provide access
for future servicing of the fittings and conduit assemblies. Fill in the boxed-in section with dry sand
to keep condensation in the satellite housing to a minimum.
Secure the dispensing unit to the island using anchor bolts through the two mounting holes, which
are 12-3/16 inches (310mm) apart and are indicated on each base layout by an X. If the
dispensing unit is not securely fastened to the island, supply line leaks at unions and pipe joints
may occur. Use one of two types of bolts to anchor the satellite to the island. Use two (2) 1/2" x
5" (13mm x 125mm) machine bolts imbedded in the concrete, or, to meet minimum UL and API
requirements for universal interchangeability of pumps, use two 1/2" x 3 1/2" (13mm x 90mm) lag
screws with 2" (51mm) expansion shields.
DISPENSER
Refer to the installation/operation manuals supplied with the dispenser for the proper installation
and operation of this unit.
•
Series 9100A Installation/Operation Manual, 035257
•
Series 9800A Installation/Operation Manual, 035296
NOZZLE, HOSE, AND ACCESSORIES
This unit is normally equipped for use with a UL-Listed interchangeable service station type
nozzle. Units equipped with suffix N are equipped for use with a UL-Listed Richards Mark XIIL
nozzle. Only UL-Listed hose assemblies and accessories are to be used with this device. A
Listed breakaway connector must be installed on all hose assemblies. On front-load twin
satellites, each start lever corresponds with the hose outlet to its right.