Geist R-Series PDU v4 User Manual

Page 17

Advertising
background image

Hardware

17

© 2014 Geist

configured for IPv6 support as well as IPv4; make sure to select the entry for the
IPv4 protocol.

Choose the Use the following IP address option, then set IP address to
192.168.123.1 and Subnet Mask to 255.255.255.0. For this initial setup, Default
Gateway
and the DNS Server entries can be left blank. Select OK, then OK again to
close both the Internet Protocol Properties and Local Properties windows.

Once the NIC settings are configured properly, you should be able to access the unit
by typing "http://192.168.123.123" into the address bar of your web browser. If you
are setting up the unit for the first time, or if the unit has been reset back to factory
defaults via the network-reset button, the unit will require you to create an Admin
account and password before you can proceed.

Once you have created the Admin account and logged into it, the unit's default
Sensors page should come up by default. Navigate to the System tab, then the
Network page to configure the device's network properties. The unit's IP Address,
Subnet Mask, Gateway, and DNS settings can either be assigned manually, or

Advertising