Nortec LINKS XPS MH User Manual

Page 44

Advertising
background image

41 | Links XPS for MHTC

Table 6: Variable Definitions

Variable Name

e

R = Read

W = Write

Description

nviCapLimit_x

W

Analog Value

Sets humidifier capacity limit (50-100%)
Example: 500 = 50%, 1000=100%

nvoCapLimit_x

R

Analog Value

Read Manual capacity (50-100%)
Example: 500 = 50%, 1000=100%

nviRHDem1_x

W

Analog Value

Writes channel 1 demand or %RH. Allows BAS control of output.
(0 - 100%). Unit must be configured to accept network demand.
Example: 500 = 50%, 1000=100%

nvoRHDem1_x

R

Analog Value

Reads channel 1 demand or %RH. Allows BAS control of output.
(0 - 100%). Unit must be configured to accept network demand.
Example: 500 = 50%, 1000=100%

nviSet1_x

W

Analog Value

Writes setpoint when humidifier is operating on
sensor/transducer controls. Acceptable values are 10 - 90 %.
Example: 500 = 50%, 900=90%

nvoSet1_x

R

Analog Value

Reads setpoint when humidifier is operating on
sensor/transducer controls. Acceptable values are 10 - 90 %.
Example: 500 = 50%, 900=90%

nviDisable_x

W

Binary Value

Allows for remote disable of humidifier.
0 = Run
1 = Disable

nvoDisable_x

R

Binary Value

Checks remote disable status.
0 = Run
1 = Disable

nviNetSensor_x

W

Binary Value

Configures unit to look for either hardwired controls or control
value written from building automation system.
0 = Hard wired controls
1 = Network controls

nvoNetSensor_x

R

Binary Value

Checks current control source.
0 = Hard Wired
1 = Network

nvoFault_x

R

Binary Value

Reads fault status.
0 = Normal operation
1 = Unit Fault

nvoSecurity_x

R

Binary Value

Checks status of security loop (on/off controls wired in series
between terminals 1 and 2 on the low voltage terminal strip).
Humidifier will only operate if loop is closed.
0 = Open
1 = Closed

nvoService_x

R

Binary Value

Checks service light status.
0 = Normal operation
1 = Service required, check humidifier display for information.

nviHum_Control_x

W

Analog Value

Change control type that humidifier is accepting.
Warning: Check physical control type before modifying.
0 = Demand signal
1 = On/Off signal
2 = Transducer (sensed %RH), humidifier uses proportional
algorithm
3 = Transducer (sensed %RH), humidifier uses proportional-
integral algorithm