Nortec LINKS XPS MH User Manual

Page 46

Advertising
background image

43 | Links XPS for MHTC

Table 7: Humidifier Variable Addresses – Unit #1

MHTC Links XPS Variable Listing and Default Settings
Default BACnet/IP Address:

192.168.10.11; Subnet: 255.255.255.0

Default BACnet/MSTP:

MAC Address = 11, Device Instance = 11

Default Johnson N2 Address:

11

Unit #1

BACnet

Lonworks

N2

Variable Name

Type Instance

SNVT

SNVT # NV Index

Type

Instance

nvoServTime_1

AV

1

SNVT_lev_count_f

55

1

Ana_Output

1

nvoPumpRunHr_1

AV

2

SNVT_lev_count_f

55

2

Ana_Output

2

nvoUVRunHr_1

AV

3

SNVT_lev_count_f

55

3

Ana_Output

3

nvoSet1_1

AV

4

SNVT_lev_count_f

55

4

Ana_Output

4

nvoHum_Control_1

AV

5

SNVT_lev_count_f

55

5

Ana_Output

5

nvoCapLimit_1

AV

6

SNVT_lev_count_f

55

6

Ana_Output

6

nvoRHDem1_1

AV

7

SNVT_lev_count_f

55

7

Ana_Output

7

nviSet1_1

AV

8

SNVT_lev_count_f

55

8

Ana_Output

8

nviRHDem1_1

AV

9

SNVT_lev_count_f

55

9

Ana_Output

9

nviHum_Control_1

AV

10

SNVT_lev_count_f

55

10

Ana_Output

10

nviCapLimit_1

AV

11

SNVT_lev_count_f

55

11

Ana_Output

11

nvoNetSensor_1

BV

1

SNVT_switch

95

12

Dig_Output

1

nvoDisable_1

BV

2

SNVT_switch

95

13

Dig_Output

2

nvoStage1Dem_1

BV

3

SNVT_switch

95

14

Dig_Output

3

nvoStage2Dem_1

BV

4

SNVT_switch

95

15

Dig_Output

4

nvoStage3Dem_1

BV

5

SNVT_switch

95

16

Dig_Output

5

nvoWarning_1

BV

6

SNVT_switch

95

17

Dig_Output

6

nvoService_1

BV

7

SNVT_switch

95

18

Dig_Output

7

nvoFault_1

BV

8

SNVT_switch

95

19

Dig_Output

8

nvoCleaning_1

BV

9

SNVT_switch

95

20

Dig_Output

9

nvoTankDrain_1

BV

10

SNVT_switch

95

21

Dig_Output

10

nvoSecurity_1

BV

11

SNVT_switch

95

22

Dig_Output

11

nvoTankLevel_1

BV

12

SNVT_switch

95

23

Dig_Output

12

nviNetSensor_1

BV

13

SNVT_switch

95

24

Dig_Output

13

nviDisable_1

BV

14

SNVT_switch

95

25

Dig_Output

14

Advertising