Nortec LINKS XPS MH User Manual

Page 51

Advertising
background image

Links XPS for MHTC | 48

Table 12: Humidifier Variable Addresses - Unit #6

Unit #6

BACnet

Lonworks

N2

Variable Name

Type Instance

SNVT

SNVT # Element

Type

Instance

nvoServTime_6 AV

56

SNVT_lev_count_f 55

126 Ana_Output

56

nvoPumpRunHr_6 AV

57

SNVT_lev_count_f 55

127 Ana_Output

57

nvoUVRunHr_6 AV

58

SNVT_lev_count_f 55

128 Ana_Output

58

nvoSet1_6

AV

59

SNVT_lev_count_f 55

129 Ana_Output

59

nvoHum_Control_6 AV

60

SNVT_lev_count_f 55

130 Ana_Output

60

nvoCapLimit_6 AV

61

SNVT_lev_count_f 55

131 Ana_Output

61

nvoRHDem1_6 AV

62

SNVT_lev_count_f 55

132 Ana_Output

62

nviSet1_6

AV

63

SNVT_lev_count_f 55

133 Ana_Output

63

nviRHDem1_6 AV

64

SNVT_lev_count_f 55

134 Ana_Output

64

nviHum_Control_6 AV

65

SNVT_lev_count_f 55

135 Ana_Output

65

nviCapLimit_6

AV

66

SNVT_lev_count_f 55

136 Ana_Output

66

nvoNetSensor_6 BV

71

SNVT_switch

95

137

Dig_Output

71

nvoDisable_6

BV

72

SNVT_switch

95

138

Dig_Output

72

nvoStage1Dem_6 BV

73

SNVT_switch

95

139

Dig_Output

73

nvoStage2Dem_6 BV

74

SNVT_switch

95

140

Dig_Output

74

nvoStage3Dem_6 BV

75

SNVT_switch

95

141

Dig_Output

75

nvoWarning_6

BV

76

SNVT_switch

95

142

Dig_Output

76

nvoService_6

BV

77

SNVT_switch

95

143

Dig_Output

77

nvoFault_6

BV

78

SNVT_switch

95

144

Dig_Output

78

nvoCleaning_6

BV

79

SNVT_switch

95

145

Dig_Output

79

nvoTankDrain_6 BV

80

SNVT_switch

95

146

Dig_Output

80

nvoSecurity_6

BV

81

SNVT_switch

95

147

Dig_Output

81

nvoTankLevel_6 BV

82

SNVT_switch

95

148

Dig_Output

82

nviNetSensor_6 BV

83

SNVT_switch

95

149

Dig_Output

83

nviDisable_6

BV

84

SNVT_switch

95

150

Dig_Output

84

Advertising
This manual is related to the following products: