Links XPS for MHTC | 50

Table 14: Humidifier Variable Addresses - Unit #8

Unit #8

BACnet

Lonworks

N2

Variable Name

Type Instance

SNVT

SNVT # Element

Type

Instance

nvoServTime_8 AV

78

SNVT_lev_count_f 55

176 Ana_Output

78

nvoPumpRunHr_8 AV

79

SNVT_lev_count_f 55

177 Ana_Output

79

nvoUVRunHr_8 AV

80

SNVT_lev_count_f 55

178 Ana_Output

80

nvoSet1_8

AV

81

SNVT_lev_count_f 55

179 Ana_Output

81

nvoHum_Control_8 AV

82

SNVT_lev_count_f 55

180 Ana_Output

82

nvoCapLimit_8 AV

83

SNVT_lev_count_f 55

181 Ana_Output

83

nvoRHDem1_8 AV

84

SNVT_lev_count_f 55

182 Ana_Output

84

nviSet1_8

AV

85

SNVT_lev_count_f 55

183 Ana_Output

85

nviRHDem1_8 AV

86

SNVT_lev_count_f 55

184 Ana_Output

86

nviHum_Control_8 AV

87

SNVT_lev_count_f 55

185 Ana_Output

87

nviCapLimit_8

AV

88

SNVT_lev_count_f 55

186 Ana_Output

88

nvoNetSensor_8 BV

99

SNVT_switch

95

187

Dig_Output

99

nvoDisable_8

BV

100

SNVT_switch

95

188

Dig_Output 100

nvoStage1Dem_8 BV

101

SNVT_switch

95

189

Dig_Output 101

nvoStage2Dem_8 BV

102

SNVT_switch

95

190

Dig_Output 102

nvoStage3Dem_8 BV

103

SNVT_switch

95

191

Dig_Output 103

nvoWarning_8

BV

104

SNVT_switch

95

192

Dig_Output 104

nvoService_8

BV

105

SNVT_switch

95

193

Dig_Output 105

nvoFault_8

BV

106

SNVT_switch

95

194

Dig_Output 106

nvoCleaning_8

BV

107

SNVT_switch

95

195

Dig_Output 107

nvoTankDrain_8 BV

108

SNVT_switch

95

196

Dig_Output 108

nvoSecurity_8

BV

109

SNVT_switch

95

197

Dig_Output 109

nvoTankLevel_8 BV

110

SNVT_switch

95

198

Dig_Output 110

nviNetSensor_8 BV

111

SNVT_switch

95

199

Dig_Output 111

nviDisable_8

BV

112

SNVT_switch

95

200

Dig_Output 112