Nortec LINKS XPS MH User Manual

Page 52

Advertising
background image

49 | Links XPS for MHTC

Table 13: Humidifier Variable Addresses - Unit #7

Unit #7

BACnet

Lonworks

N2

Variable Name

Type Instance

SNVT

SNVT # Element

Type

Instance

nvoServTime_7 AV

67

SNVT_lev_count_f 55

151 Ana_Output

67

nvoPumpRunHr_7 AV

68

SNVT_lev_count_f 55

152 Ana_Output

68

nvoUVRunHr_7 AV

69

SNVT_lev_count_f 55

153 Ana_Output

69

nvoSet1_7

AV

70

SNVT_lev_count_f 55

154 Ana_Output

70

nvoHum_Control_7 AV

71

SNVT_lev_count_f 55

155 Ana_Output

71

nvoCapLimit_7 AV

72

SNVT_lev_count_f 55

156 Ana_Output

72

nvoRHDem1_7 AV

73

SNVT_lev_count_f 55

157 Ana_Output

73

nviSet1_7

AV

74

SNVT_lev_count_f 55

158 Ana_Output

74

nviRHDem1_7 AV

75

SNVT_lev_count_f 55

159 Ana_Output

75

nviHum_Control_7 AV

76

SNVT_lev_count_f 55

160 Ana_Output

76

nviCapLimit_7

AV

77

SNVT_lev_count_f 55

161 Ana_Output

77

nvoNetSensor_7 BV

85

SNVT_switch

95

162

Dig_Output

85

nvoDisable_7

BV

86

SNVT_switch

95

163

Dig_Output

86

nvoStage1Dem_7 BV

87

SNVT_switch

95

164

Dig_Output

87

nvoStage2Dem_7 BV

88

SNVT_switch

95

165

Dig_Output

88

nvoStage3Dem_7 BV

89

SNVT_switch

95

166

Dig_Output

89

nvoWarning_7

BV

90

SNVT_switch

95

167

Dig_Output

90

nvoService_7

BV

91

SNVT_switch

95

168

Dig_Output

91

nvoFault_7

BV

92

SNVT_switch

95

169

Dig_Output

92

nvoCleaning_7

BV

93

SNVT_switch

95

170

Dig_Output

93

nvoTankDrain_7 BV

94

SNVT_switch

95

171

Dig_Output

94

nvoSecurity_7

BV

95

SNVT_switch

95

172

Dig_Output

95

nvoTankLevel_7 BV

96

SNVT_switch

95

173

Dig_Output

96

nviNetSensor_7 BV

97

SNVT_switch

95

174

Dig_Output

97

nviDisable_7

BV

98

SNVT_switch

95

175

Dig_Output

98

Advertising
This manual is related to the following products: