Vav/cav controller configuration, Vav/cav confi guration screens, Vav/cav/mua operator interface sd – Orion System VAV II Controller v.1 User Manual

Page 27

Advertising
background image

VAV/CAV/MUA Operator Interface SD

VAV/CAV CONTROLLER CONFIGURATION

27

VAV/CAV Confi guration Screens

Confi guration Screen #10 - Supply Air

Setpoint Reset Source

VAV/CAV Cnfg ID 0001

Reset SAT Stpt Using
Input Voltage Signal
Use < Or > To Change

Select the desired method of resetting the Heating/Cooling Supply Air
Setpoint. Default is Input Voltage Signal. Available selections are:

• Input

Voltage

Signal

• Outdoor

Air

Sensor

• Space

Sensor

• Fan

VFD

Percentage

• Local

Analog

Value

• Return

Temp

Sensor

Confi guration Screen #11 - Type of

CO

2

Sensor Installed

VAV/CAV Cnfg ID 0001

CO2 Sensor Installed

Sensor Type: NONE

Use < Or > To Change

You can install a CO

2

Sensor on this HVAC unit to monitor the Carbon

Dioxide levels and/or to provide for Indoor Air Quality (IAQ) con-
trol. If you only want to monitor the level, enter the same Maximum
Economizer Position that you set for the Minimum Position and it will
not be reset as the CO

2

level increases. If you do want IAQ control, set

the desired Maximum Economizer Position to reset up to during high
levels of CO

2

. The VAV/CAV Controller needs to know what type of

CO

2

Sensor signal output is being provided. Select either VDC (0-10)

or mA (4-20) as the CO

2

Sensor signal. Select NONE if no CO

2

sensor

is used. Default is NONE.

Confi guration Screen #12 - CO2 Sensor

Maximum Reading

VAV/CAV Cnfg ID 0001

CO2 Sensor Maximum

Reading: 2000ppm

Enter 0 If No Sensor

The VAV/CAV Controller needs to know the CO

2

Sensor scaling for

proper reading of the CO

2

Sensor output. The Standard CO

2

Sensor

should be scaled to 2000 PPM. Enter

<0>

if no CO

2

Sensor is being

used. Default is 2000ppm.

Confi guration Screen #13 - Air to Air Heat

Pump Control

VAV/CAV Cnfg ID 0001

Air to Air Heat Pump

Control: No

Use < Or > To Change

The VAV/CAV Controller can be confi gured to operate as an Air To Air
Heat Pump Controller. If you make this selection, the same relays are
used to stage the compressors in both the Heating and Cooling Modes.
The only difference is that a separate Reversing Valve relay will activate
in the Heating Mode to enable Heating to occur. You must confi gure at
least one relay for the reversing valve.

You can also confi gure for an Auxiliary Heat relay that will activate
whenever the Supply Air drops below the Supply Setpoint by 5°F to
provide Heat when the Outdoor Air is too cold for the Heating Mode to
operate correctly. Default is No.

Confi guration Screen #14 - Broadcast Time

Clock to All Loop Units

VAV/CAV Cnfg ID 0001

Broadcast Time Clock

To Loop Units: No

Use < Or > To Change

This setting enables the VAV/CAV Controller to send its real time clock
information to all controllers on the local loop. This must be used when
connecting VAV/Zone Controllers on the local loop, but can be used to
synchronize clock time in all controllers on the local loop.

Confi guration Screen #15 - Broadcast Outdoor

Temperature

VAV/CAV Cnfg ID 0001

Broadcast Outside

Temperature: No

Use < Or > To Change

This setting enables the VAV/CAV Controller to send its Outdoor Air
Temperature reading to all other controllers on the entire system. It is
specifi cally used when more than one HVAC unit is installed and only
one Outdoor Air Sensor is used to supply its signal to all controllers.
Default is No.