Mua ii controller configuration, Mua ii confi guration screens – Orion System VAV II Controller v.1 User Manual

Page 43

Advertising
background image

VAV/CAV/MUA Operator Interface SD

MUA II CONTROLLER CONFIGURATION

43

Confi guration Screens

In order to correctly set up the Unit Controller, you must fi rst confi gure
several parameters in regard to the type of HVAC unit and system you
have installed. Most of these values and operating parameters are only
set once at the initial system setup and are never changed.

Confi guration Screen #1 - Proof of Flow

Switch Installed

MUA-II Cnfg 0001

Proof of Flow Switch

Installed: No

Use < Or > To Change

If you need proof of airfl ow before allowing any Heating or Cooling
Stages to operate, install a Differential Pressure Switch with a contact
closure that is connected to analog input #7 and select this option. If this
option is not selected, the air handler assumes there is adequate airfl ow
any time the fan is running and ignores this signal causing analog input
#7 to default to Space Humidity. Default is No.

Confi guration Screen #2 - Outdoor Air

Humidity Sensor Installed

MUA-II Cnfg 0001

OA Humidity Sensor

Installed: No

Use < Or > To Change

This confi guration screen allows you to indicate whether an Outdoor Air
Humidity Sensor is to be installed and used to calculate Dewpoint set-
tings. If you either don’t have an Outdoor Air Humidity Sensor installed
or have one installed but wish to use only Drybulb Temperatures for
control of the HVAC unit, the setting should be set to No. If you have
an Outdoor Air Humidity Sensor installed and wish to use Dewpoint
calculations for unit control, select Yes. If you have a sensor installed
and do not select Yes, the sensor readings will be ignored. Default is No.

Confi guration Screen #3 - Heat In Dehumidify

Control

MUA-II Cnfg 0001

Heat In Dehumidify

Installed: No

Use < Or > To Change

If you need to allow Heat during Dehumidifi cation, select this option. If
this option is not selected, the controller assumes that only Reheat will
be allowed during Dehumidifi cation Mode. Default is No.

Confi guration Screen #4 - If External Heat,

Output Range

MUA-II Cnfg 0001

If External Heat

Output Range: 0-10V

[0= 2-10V 1= 0-10V]

If you have an External Heating device to be controlled by the MUA II
Controller, you can select between the voltage ranges that will be used
to control the device. The available options are 2-10 VDC and 0-10
VDC. Default is 0-10V.

Confi guration Screen #5 - Is External Heat,

Reverse Acting

MUA-II Cnfg 0001

Is External Heat

Reverse Acting: No

Use < Or > To Change

If you need the modulation of the External Heat to be Reverse Acting,
select this option. If this option is not selected, the controller assumes
the modulation will be Direct Acting. Default is No.

Confi guration Screen #6 - Broadcast Outdoor

Temperature

MUA-II Cnfg 0001

Broadcast Outside

Temperature: No

Use < Or > To Change

If you have other unit controllers on the system, you can elect to Broad-
cast the Outdoor Air Temperature to these units by selecting Yes on this
screen. If you don’t have other controllers or they have their own Outdoor
Air Temperature Sensors, select No. Default is No.

MUA II Confi guration Screens

Advertising