VAV/CAV/MUA Operator Interface SD

MUA II CONTROLLER SETPOINTS

49

The Push-Button Override Duration Setpoint allows you to adjust the
amount of time the Override will remain in effect when the Override
Button is pressed. To cancel the Override before the Override Duration
time period expires, press the Override Button for 5 to 10 seconds.

Description

Minimum

Default

Maximum

Push-Button

Override Duration

0.0 Hr

2.0 Hr

8.0 Hr

Setpoint Screen #17 - HVAC Mode Sensor

Slide Offset

MUA II SPTS 0001

Slide Offset Sensor

Setpoint....: 0ºF

If the Unit Controller has a Space Temperature Sensor with the Slide
Adjust option installed, the HVAC Mode Enable Heating and Cooling
Setpoints can be offset by the HVAC Mode Sensor Slide Offset Setpoint
value. When the Slide Adjust bar is in the middle, no offset will occur.
If the Slide Adjust bar is moved all the way to the top of the Sensor, the
Heating and Cooling Setpoints will be raised by the Setpoint value you
have entered. If the Slide Adjust bar is moved all the way down to the
bottom of the Sensor, the Heating and Cooling Setpoints will be lowered
by the Setpoint value you have entered.

Description

Minimum

Default

Maximum

HVAC Mode Sensor

Slide Offset

0ºF

0ºF

10ºF

Setpoint Screen #18 - HVAC Schedule

MUA II SPTS 0001

AHU Scheduled By
Schedule Num: 0
0=AHU 1-7=Scheduler


Normally, the MUA II Controller will use its own internal time clock
and week schedules to set the Occupied Mode of operation. If you have
several air handlers, you can connect an external scheduling device to
the communications loop and program the air handler for the desired
schedule. If the MUA II Controller is using its internal schedule, enter

<0>

for Internal.

Description

Minimum

Default

Maximum

Schedule Number

0

0

1 to 7

MUA II Setpoint Screens

Setpoint Screen #19 - Supply Fan Starting

Delay Timer

MUA II SPTS 0001

Fan Time Delay

Before Activation
Can Occur..: 60s

This is the time delay that occurs before the fan is activated when the
unit switches into the Occupied Mode from Unoccupied Mode.

Description

Minimum

Default

Maximum

Fan Start Delay Timer

1 Sec

60 Sec

180 Sec

Setpoint Screen #20 - Sensor Calibration for

SAT & OAT

MUA II SPTS 0001

Sensor Calibration

SAT: XX.X 0.0
OAT: XX.X 0.0

The Thermistor Type III temperature sensors connected to the MUA II
Controller can be calibrated using this screen. Enter a Positive value to
increase a reading and a Negative value to decrease a reading

Description

Minimum

Default

Maximum

Sensor Calibration SAT

-100.0ºF

0.0ºF

+100.0ºF

Sensor Calibration OAT

-100.0ºF

0.0ºF

+100.0ºF

Setpoint Screen #21 - Sensor Calibration

Reset for SPC

MUA II SPTS 0001

Sensor Calibration

Reset Sensor

SPC: XX.X 0.0

If you are using a temperature sensor connected to analog input #1 on the
MUA II controller for resetting the Supply Air Temperature, the Therm-
istor Type III temperature sensor connected to the MUA II Controller
can be calibrated using this screen. Enter a Positive value to increase a
reading and a Negative value to decrease a reading.

Description

Minimum

Default

Maximum

Sensor Calibration SPC

-100.0ºF

0.0ºF

+100.0ºF