Minilink pd status, Minilink pd confi guration & status screens, Vav/cav/mua operator interface sd 64 – Orion System VAV II Controller v.1 User Manual

Page 64

Advertising
background image

Zone

Zone

MINILINK PD STATUS

VAV/CAV/MUA Operator Interface SD

64

MiniLink PD Confi guration & Status Screens

Confi guration Screen #4 - Optimal Start

Target Zone

Polling Unit Config

Optimal Start

Target Zone..: XX

[Enter Target Zone]

This is the unit ID of the Zone that you want to be satisfi ed by the normally
scheduled start time. If you enter “-1” into this box, it will average all
zones instead of picking a specifi c zone. If you do not require Optimal
Start, enter “0”. Valid entry is -1 to 58.

Confi guration Screen #5 - Maverick Testing

Polling Unit Config

Maverick Testing

Disabled: YES

Use < Or > To Change

Select YES or NO. Disabling the Maverick Testing allows known troubled
zone(s) to continue voting without causing a Maverick alarm. In other
words, all zones are included in the voting regardless of whether they are
more than four degrees from setpoint.

Confi guration Screens #6-65 - Alarm Polling

Polling Unit Config

Enable Alarm Polling

Unit XX: YES

Use < Or > To Change

Select YES or NO. Enabling Alarm Polling allows any alarm from the
loop to be polled. You must set this for each controller on the loop.

MiniLink PD Status

Status Screen #1 - Schedule Mode, System

Status, and Minutes Left

Polling Device

System Occupied

Venting Mode

XXX Min Left in Mode

Line 2 Current Schedule Mode

Can be System Occupied or System Unoccupied.

Line 3

Currently System Status

Can be Vent Mode, Cooling Mode, or Heat Mode.

Line 4

Minutes Left In Mode

The number of minutes left in the current mode of

operation before it can switch modes. This value is

user-adjustable.

See

Confi guration Screen #3 on

page 63.

Status Screen #2 - Mode Priority, Cool Total,

and Heat Total

Polling Device

No Mode Priority

Cool Total.: XX.XºF
Heat Total.: XX.XºF

Line 2 Mode Priority

Can be Heat Priority or Cool Priority. This is based on

the voting zones and their demand.

Line 3

Cool Total

Total cooling temperature demand from all zones.

Line 4

Heat Total

Total heating temperature demand from all zones.

Advertising