MUA II CONTROLLER SETPOINTS

VAV/CAV/MUA Operator Interface SD

46

MUA II Setpoint Screens

Setpoint Screen #1 - Supply Air

Temperature Setpoint

MUA II SPTS 0001

Supply Air Temp

Setpoint...: 70ºF

The Supply Air Setpoint is the desired temperature to be delivered by
the MUA II at any time during the Occupied Mode of operation.

Description

Minimum

Default

Maximum

Supply Air Temp

Setpoint

50ºF

70ºF

90ºF

Setpoint Screen #2 - Staging Deadbands

MUA II SPTS 0001

Staging

Deadbands

Cooling.....: 5ºF
Heating.....: 5ºF

The Cooling Deadband added to the Supply Air Setpoint is the Cooling
Mode Setpoint.

When the Outside Air Temperature rises above this setpoint, the MUA
II will go into Cooling Mode. The Heating Deadband is subtracted from
the Supply Air Setpoint to get the Heating Mode Setpoint.

When the Outside Air Temperature drops below this setpoint, the MUA
II will go into Heating Mode.

Description

Minimum

Default

Maximum

Cooling Deadband

2ºF

5ºF

20ºF

Heating Deadband

2ºF

5ºF

20ºF

Setpoint Screen #3 - Unoccupied Deadbands

MUA II SPTS 0001

Unoccupied Deadbands

Cooling.....: 0ºF
Heating.....: 0ºF

During the Unoccupied Mode, these values will be added to the Cool-
ing Setpoint and subtracted from the Heating Setpoint. These settings
are only used if the controller has been confi gured to utilize a Space
Temperature Sensor.

Description

Minimum

Default

Maximum

Unoccupied Cooling Deadband

0ºF

0ºF

30ºF

Unoccupied Heating Deadband

0ºF

0ºF

30ºF

Setpoint Screen #4 - Systems with Reheat -

Dewpoint Control Setpoint

MUA II SPTS 0001

Systems with Re-heat

Dewpoint Control

Setpoint...: 55ºF

The systems capable of Dehumidifi cation will enter this mode of opera-
tion when the Outside Air Dewpoint rises above the Dewpoint Setpoint.

Description

Minimum

Default

Maximum

Dewpoint Setpoint

40ºF

55ºF

80ºF

Setpoint Screen #5 - Enthalpy Staging -

Deadband and Hysteresis

MUA II SPTS 0001

Enthalpy Staging

Deadband....: 5BTU
Hysteresis..: 1.0BTU

The Enthalpy Deadband is the amount of Enthalpy in the Outside Air
needed to activate an extra stage of cooling. The Enthalpy Hysteresis
is used to avoid unnecessary cycling of the Cooling Stages when the
Outside Enthalpy is close to the setpoint.

Description

Minimum

Default

Maximum

Enthalpy Deadband

3 BTU

5 BTU

20 BTU

Enthalpy Hysteresis

0.5 BTU

1.0 BTU

2.5 BTU

Setpoint Screen #6 - Heat Delay During

Dehumidifi cation

MUA II SPTS 0001

Heat Delay During

Dehumidification

Will Occur..: 2 Min

If Heating during Dehumidifi cation is confi gured, this is the amount
of time the Heating call will be delayed after the Dehumidifi cation is
activated.

Description

Minimum

Default

Maximum

Heat Delay

0 Min

2 Min

10 Min