Dual electronic expansion valve module, Diagnostics – Orion System Dual Electronic Expansion Valve Module User Manual

Page 10

Advertising
background image

Dual Electronic Expansion Valve Module

Technical Guide

10

LED Descriptions

The Dual Electronic Expansion Valve Module is equipped with LEDs
that can be used to verify operation and perform troubleshooting. There
are LEDs for communication, operation modes, and diagnostic codes.
The module has 11 LEDs—1 used for E-BUS communications, 8 used
for operation & status, and 2 used for alarms.

See Figure 4 for the LED locations. The LEDs associated with these
inputs and outputs allow you to see what is active without using a volt-
meter. The LEDs and their uses are as follows:

Operation LEDs

POWER - This green LED will light up to indicate that 24 VAC power
has been applied to the module.

STATUS - This green LED will light up and blink the board address
at startup.

Diagnostic LEDs

ALARM - This red LED will light up to indicate an alarm. The type of
alarm will display on the LCD display. The ALARM LED also blinks
when the expansion valve is initializing at startup.

Alarms

The controller may have the following alarms for each refrigerant circuit:

Low Suction Pressure

This alarm will be activated when the suction pressure

drops below 70 PSIG for longer than 10 seconds.Valve

will modulate by 10% one time when alarm occurs to

try to get suction pressure back up. This alarm will

cease when Suction Pressure is above 70 PSIG.

High Superheat

This alarm will be activated when the Superheat

reaches 25 degrees for longer than 60 seconds. This

alarm will not affect valve operation. This alarm will

cease when the Superheat drops below 25 degrees.

Low Superheat

This alarm will be activated when the Superheat

is 0 degrees for longer than 60 seconds. This alarm

will not affect valve operation. This alarm will cease

when the Superheat rises above 0 degrees.

Alarm LED’s will blink and the specifi c alarm can be accessed on the
LCD display. Also, the Relay will activate for the specifi c valve that
has the alarm.

Diagnostics