Status V-A/B and V-A/B Alarm Screens

Status V-A & V-B Screens

Refer to the following map when navigating through the Status Valve
A Screens. From the STATUS V-A or STATUS V-B Screen, press

<ENTER> to scroll through the screens.

STATUS

V-A/B

V-A/B MODE

ON/OFF/FORCE

V-A/B POS
0 TO 100%

SUPRHEAT

XX.X

SUPRHEAT SP

O TO 25

COIL TMP

XX.X

CALC TMP

XX.X

SUC PRESS

XXX

V-A & V-B Alarm Screens

Refer to the following map when viewing Valve A and Valve B Alarm
Screens. These screens will display automatically when alarms are
present.

V-A/B

ALARMS

CURRENT SUPERHEAT CALCULATION

SUPERHEAT SETPOINT SETTING

0 to 25

COIL TEMPERATURE READING FROM

TEMPERATURE SENSOR INPUT

CALCULATED COIL TEMPERATURE

FROM SUCTION PRESSURE INPUT

SUCTION PRESSURE READING

FROM INPUT

VALVE A/B MODES: ON ,OFF, FORCE

ON: Valve is modulating to maintain Superheat.

OFF: System is off.

FORCE: Valve is set to a forced position.

VALVE POSITION

0 to 100 percent

ALARMS

The alarms are as follows:

NO V-A/B ALARMS:

This will be shown if there are no current alarms.

LO SPRESS:

This indicates a Low Suction Pressure Alarm condition

which is activated when the Suction Pressure drops below 70 PSIG for
longer than 10 seconds. The valve will modulate by 10% one time when
alarm occurs to try to increase the suction pressure. This alarm will dis-
able when Suction Pressure is above 70 PSIG.

HI SHEAT:

This alarm will be activated when the Superheat reaches

25 degrees for longer than 60 seconds. This alarm will not affect valve
operation. This alarm will disable when the Superheat drops below 25
degrees.

LO SHEAT:

This alarm will be activated when the Superheat is 0

degrees for longer than 60 seconds. This alarm will not affect valve
operation. This alarm will disable when the Superheat rises above 0 de-
grees