Dual electronic expansion valve module, Aaon, Unit start-up procedures – Orion System Dual Electronic Expansion Valve Module User Manual

Page 5: Technical guide

Advertising
background image

Technical Guide

Dual Electronic Expansion Valve Module

5

AAON

®

Unit Start-Up Procedures

AAON

®

Unit Start-Up Procedures

NOTE: The following instructions were provided by AAON to set

up the unit. If you have any questions about this start-up
procedure, please contact AAON Technical Support.

Refrigeration Charging Sequence:

1. Determine valve size utilized on equipment part number from the

physical valve. There are currently 4 models used:

SER-C (5-Ton Maximum Nominal Capacity)

SER-D (13-Ton Maximum Nominal Capacity)

SER-G (26-Ton Maximum Nominal Capacity)

SER-J (48-Ton Maximum Nominal Capacity)

2. Determine circuit capacity and divide by valve Maximum

Nominal Capacity to determine average full refrigerant mass fl ow

Example: CC-B-045 Condensing unit; (2) 22.5 Ton Circuits,
Evaporator contains (2) SER-G EEV (Electronic Expansion Valve)

22.5/26 = 0.865 = 86.5%, Rounded to 87%

NOTE: Consult with System Specifi cation and Unit Rating, as

lower or higher evaporator temperatures and other factors
play a role in the actual capacity the compressors may
deliver.

3. Ensure system is charged to a reasonable point to enable

compressor start and ensure that all other procedures dictated for
installation and startup have been followed from the unit IOM.

4. Set the EEV Module’s Valve to manual override position of 87%.

5. Ensure the space is fully loaded at design conditions to allow for

maximum capacity operation and lock the compressor to fully-
loaded capacity.

6. Energize the compressor and ensure a solid column of liquid to the

EEV via verifi cation at the sight glass.

7. From the point of a full sight glass, follow standard charging

procedures to maximize effi ciency via sub cooling, and delta T at
the evaporator.

8. Disable the manual override position on the EEV Module and

allow automatic operation at the desired set point.

9. Verify superheat operation and consistent solid column of liquid at

the sight glass. This may take up to 15 minutes.

10. Repeat instruction for Valve 2 starting with Step 3.

Fine-Tuning the EEV Module’s Setpoints for Best

Reaction Time and Effi ciency:

1. Ballpark the modulation rate based on line set length using the

following table as a guide:

Line Set Length

Modulation Rate

15

15

30

20

45

30

60

35

75

40

90

45

120

50

2. Ensure the outside air temperature, return air temperature, and

control setpoints do not change during calibration and fi ne-tuning
procedures.

3. Power off the EEV Module completely to ensure the smart-start

routine does not skew the initial position of future tests.

4. Power on the EEV Module and initialize the unit to enable

compressor operation.

5. Monitor superheat on the EEV Module and mark the time system

started until superheat is maintained at a steady state within an
acceptable dead band for more than 60 seconds.

6. Note the time from startup to stable superheat as well as the

current modulation rate set point (this process should not take lon-
ger than 20 minutes. If it does, then check unit charge or unstable
operating conditions).

7. Adjust the modulation rate set point by 2-3 seconds in either

direction and repeat test from Step 4.

8. Compare and adjust change until the best modulation rate is

obtained for the fi nal setting.

Table 1: Modulation Rate Table

Advertising