Dual Electronic Expansion Valve Module

Technical Guide

4

Features and Applications

Features

The

Dual Electronic Expansion Valve Module

provides the following:

Contains a 2x8 LCD character display and 4 buttons
that allow for status display, setpoint changes, and
confi guration changes.

Can control two electronic expansion valves independently.

Monitors suction pressure and coil temperature and
modulates electronic expansion valves to maintain
superheat.

Provides active relays to monitor valve alarms.

NOTE: The

Dual Electronic Expansion Valve Module

contains

no user-serviceable parts. Contact qualifi ed technical per-
sonnel if your

Dual Electronic Expansion Valve Module

is not operating correctly.

Adjustable Setpoints

The following describes some of the setpoints available for adjustment
using the LCD display on the Dual Electronic Expansion Valve Module:

Superheat Setpoint - One setpoint is used for

both

valves.

Modulation Rate - This setpoint (in seconds) will

adjust how often the modulation routine will make a

valve

adjustment.

Proportional Window - This setpoint (in degrees)

will adjust how much of an adjustment will be made

according to how far away it is from setpoint.

Confi guration Settings

Board Address – Can be addressed from 1 to 4.

Used as stand-alone, the default address is 1.

Valve B Enable – When using the module for only

one valve, valve B can be disabled so false information

is not displayed such as alarms and sensor readings.

Valve Steps – Confi gurable for what valve is being

used (1596, 2500, 3193, 6386)

Max Valve Position – The maximum position each

valve will modulate (%).

Min Valve Position – The minimum position each

valve will modulate (%).


Suction Pressure A Calibration Offset

Adjustable between -10 and 10 PSI.

Suction Pressure B Calibration Offset

Adjustable between -10 and 10 PSI.