Dual electronic expansion valve module, Inputs and outputs – Orion System Dual Electronic Expansion Valve Module User Manual

Page 8

Advertising
background image

Dual Electronic Expansion Valve Module

Technical Guide

8

Inputs and Outputs

Table 2: Dual Electronic Expansion Valve Module
Inputs & Outputs

I/O Map

The following inputs and outputs are available on the Dual Electronic
Expansion Valve Module. See Table 2 below to reference the Input/
Output Map.

Stand-Alone Input Commands

Valve A Enable On/Off

A 24 volt signal to Binary Input #1 initiates the Valve A Enable
function. Once Valve A is enabled, it tries to maintain the desired
Superheat Setpoint. Valve A maintains the Superheat Setpoint un-
til it loses the enable signal which then puts Valve A in Off mode.

Valve B Enable On/Off

A 24 volt signal to Binary Input #2 initiates the Valve B Enable
function. Once Valve B is enabled, it tries to maintain the desired
Superheat Setpoint. Valve B maintains the Superheat Setpoint un-
til it loses the enable signal which then puts Valve B in Off mode.

Binary Inputs

1

Valve A Enable

2

Valve B Enable

Binary Outputs

1

Valve A Alarm Relay

2

Valve B Alarm Relay

Analog Inputs

1

Coil A Temperature

2

Coil A Suction Pressure

3

Coil B Temperature

4

Coil B Suction Pressure

Stepper Motor Outputs

1

Expansion Valve A

2

Expansion Valve B