WSHP-X Module

Technical Guide

10

Installation & Wiring

VCM-X WSHP E-BUS or SA E-BUS

Controller to WSHP-X Module Wiring

for Single Water Circuit

The WSHP-X Module connects to the E-BUS Controller using a modular
HSSC cable. The WSHP-X Module requires a 24 VAC power connection
with an appropriate VA rating. See Figure 6 below for wiring.

Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS
port or can be daisy-chained together using HSSC cables.

NOTE: When using the WSHP-X Module, all compressors

will be wired from the WSHP-X Module, not the
VCM-X WSHP E-BUS Controller.

Figure 6: VCM-X E-BUS Controller to WSHP-X Module Wiring Diagram for Single Water Circuit

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

WARNING!! Observe Polarity! All
boards must be wired with GND-
to-GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.

HSSC Cable

Connect To VCM-X WSHP

E-BUS Controller

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

OE334-26-WSHPX-A Water Source

Heat Pump X Module

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R4
R5

R3

R2

COMM

COMP. B1 ENABLE
COMP. B2 ENABLE

ALARM OUTPUT

HVAC UNIT
CONNECTIONS

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.

HSSC Cable

DIGITAL STG 1 (1.5-5V)

AO1
AO2

DIGITAL STG 2 (1.5-5V)

GND

T1

WATER POF

BIN6

COM

E

LEAVING WATER TEMPERATURE

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHPX-A WSHP-X MODULE

AAON NO.: V18330

WattMaster Label

#SW000054

Rev.: 1A

E-BUS

CONNECT

E-BUS

CONNECT

+24

V

AC

GND

www.orioncontrols.com

www.aaon.com

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

- COMP. A1 EN.

- HEAT ENABLE

- COMP. A2 EN.

- WATER POF

- COMP. B1 EN.

- WATER POF

- COMP. B2 EN.

- COMMON

T 1

T 2

GND

- LEAVING WATER TEMP A

- GROUND

- LEAVING WATER TEMP B

AO1

A2O

STAGE 1- COMP. A1/B1-

STAGE 2 - COMP. A2/B2

DIGITAL COMP. A1, A2, B1, B2

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5
RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO CNTLR C2 TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

SIG 1

GND

+V

BK

RD
WH

CIRCUIT A
SUCTION PRESSURE
TRANSDUCER

SIG 1

GND

+V

BK

RD
WH

CIRCUIT B
SUCTION PRESSURE
TRANSDUCER