WSHP-X Module

Technical Guide

12

Installation & Wiring

VCM-X WSHP or SA Controller to

WSHP-X Module Wiring for Dual

Water Circuit

The VCM-X WSHP Controller or SA Controller communicates with the
WSHP-X Module using the E-BUS Distribution Module. See Figure 7
for wiring details (VCM-X WSHP Controller shown).

Figure 7: VCM-X WSHP Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit

NOTE: When using the WSHP-X Module, all compressors

will be wired from the WSHP-X Module, not the
VCM-X WSHP Controller or SA Controller.

Connect To

E-BUS

Distribution

Module

Line Voltage

24 VAC

GND

Line Voltage

All Comm Loop Wiring Is

Straight Thru

24VAC

GND

Local Loop

RS-485

9600 Baud

See Individual Component

Wiring Diagrams For

Detailed Wiring Of Analog

Inputs And Outputs

For Stand Alone Applications,
Connect To System Manager.

For Network Applications

Connect To Next Controller

And/Or MiniLink PD On Local Loop.

G - Fan ON/OFF Only

R - 24VAC

Relay Output Contacts
R2 Through R5 May Be User Configured
For The Following:
1 - Heating Stages
2 - See Note 1 Below
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel
Note: 1.) When Using the WSHP-X Module,
All Compressors Will Be Wired From the
Module, Not the VCM-X Controller.
2.) A Total Of 20 Relays Are Available By
Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User
Configurable As Listed Above.

Connect FRP Tubing To High Pressure
Port (Bottom Tube) And Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere

OE271

Static Pressure

Transducer

Splice If Required

Connect To E-BUS Distribution Module Or
Expansion Module(s)
(When Used)

Connect To Digital Room Sensor And/Or
Digital CO Sensor

2

Warning: 24 VAC Must Be Connected So That All
Ground Wires Remain Common. Failure To Do
So Will Result In Damage To The Controllers.

T to T, R to R & SHLD to SHLD

Size Transformer For Correct
Total Load.
VCM-X Controller = 8 VA

(OE332-23-WSHP-A)

VCM-X WSHP Controller

Note:
All Relay Outputs Are Normally Open And Rated
For 24 VAC Power Only.
1 Amp Maximum Load.

AI1

AI1 SET

A

I2 SET

A

I3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

Jumpers