Wshp-x module, Setpoint screens, Technical guide – Orion System Water Source Heat Pump X Module User Manual

Page 25: Setpoint status screens

Advertising
background image

Technical Guide

WSHP-X Module

25

Setpoint Screens

Setpoint Status Screens

Refer to the following map when navigating through the Setpoint Sta-
tus Screens. From the SETPOINTS Screen, press

<ENTER>

to scroll

through the screens.

NOTE: The following screens are Status Screens. The Setpoints

can’t be changed from these screens.

SETPOINTS

LOWSP HT

XXX-XXX PSI

LOWSP CL

57 PSI or

85 PSI

LOW SUCTION PRESSURE HEAT MODE SETPOINT

See Table below.

Glycol %

Low Suction

Heat Setpoint

Glycol %

Low Suction

Heat Setpoint

0% (R22)

57 PSI

20%

75 PSI

0% (410A)

100 PSI

25%

65 PSI

5%

93 PSI

30%

58 PSI

10%

87 PSI

35%

49 PSI

15%

82 PSI

40%

45 PSI

LOW SUCTION PRESSURE COOL MODE SETPOINT

See Table below.

UNSAFESP

40 PSI

UNSAFE SUCTION PRESSURE SETPOINT

See Table below.

GLYCOL

xx%

GLYCOL SETPOINT

0%, 5%, 10%, 15%, 20%, 25%, 30%, 35%, 40%

REFRIGNT

410A or R22

REFRIGERANT

401A or R22

(If R22, Glycol Setpoint will default to 0%)

LOW H2O

XX DEG

LOW LEAVING WATER TEMPERATURE SETPOINT

See Table below.

Refrigerant

Low Suction

Cool Setpoint

Refrigerant

Low Suction

Cool Setpoint

R410A

85 PSI

R22

57 PSI

Refrigerant

Unsafe

Suction

Setpoint

Refrigerant

Unsafe

Suction

Setpoint

R410A

40 PSI

R22

20 PSI

Glycol %

Low Leaving

Water

Temperature

Setpoint

Glycol %

Low Leaving

Water

Temperature

Setpoint

0% (R22)

37

º

F

20%

20

º

F

0% (410A)

37

º

F

25%

15

º

F

5%

34

º

F

30%

9

º

F

10%

30

º

F

35%

2

º

F

15%

27

º

F

40%

0

º

F