Technical Guide

WSHP-X Module

13

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

WARNING!!
Observe Polarity! All boards
must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity
could result in damage to the
boards.

OE365-23-EBD E-BUS

Distribution Module

GND

-COMM

SHLD

+COMM

INPUT

+COMM

SHLD

-COMM

GND

+VDC

485 DRV

24VAC

GND

PWR

YS102308
REV 1
I2C TO COMM
DIST. BOARD

OUTPUT

Modular Cable

Connect To

VCM-X WSHP Controller

OE334-26-WSHPX-A Water Source

Heat Pump X Module

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R4
R5

R3

R2

COMM

COMP. B1 ENABLE
COMP. B2 ENABLE

ALARM OUTPUT

HVAC UNIT
CONNECTIONS

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

Connect To Other

WattMaster-Approved

E-BUS Expansion

Module(s)

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.

HSSC Cable

DIGITAL STG 1 (1.5-5V)

AO1
AO2

DIGITAL STG 2 (1.5-5V)

GND

T1

CIRCUIT A1

SUCTION PRESSURE TRANSDUCER

BK

RD

WH

WATER POF A

BIN6

COM

CIRCUIT A2

SUCTION PRESSURE TRANSDUCER

BK

RD

WH

E

CIRCUIT B1

SUCTION PRESSURE TRANSDUCER

BK

RD

WH

CIRCUIT B2

SUCTION PRESSURE TRANSDUCER

BK

RD

WH

LEAVING WATER TEMPERATURE

FOR SYSTEM B

LEAVING WATER TEMPERATURE

FOR SYSTEM A

T2

BIN7

WATER POF B

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHPX-A WSHP-X MODULE

AAON NO.: V18330

WattMaster Label

#SW000054

Rev.: 1A

E-BUS

CONNECT

E-BUS

CONNECT

+24

V

AC

GND

www.orioncontrols.com

www.aaon.com

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

- COMP. A1 EN.

- HEAT ENABLE

- COMP. A2 EN.

- WATER POF

- COMP. B1 EN.

- WATER POF

- COMP. B2 EN.

- COMMON

T 1

T 2

GND

- LEAVING WATER TEMP A

- GROUND

- LEAVING WATER TEMP B

AO1

A2O

STAGE 1- COMP. A1/B1-

STAGE 2 - COMP. A2/B2

DIGITAL COMP. A1, A2, B1, B2

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5
RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO CNTLR C2 TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

Installation & Wiring

Figure 7, cont.: VCM-X WSHP Controller to WSHP-X Module Wiring Diagram for Dual Water Circuit