Wshp-x module, Sequence of operation modes of operation – Orion System Water Source Heat Pump X Module User Manual

Page 19

Advertising
background image

Technical Guide

WSHP-X Module

19

Sequence of Operation

Modes of Operation

NOTE: See the Unit Confi gurations Chart on page 16 for more

information about compressor staging.

Digital Stage 1 / Digital Stage 2

On units with two Digital Scroll Compressors, the fi rst compressor (A1)
will be designated as Digital Stage 1 and the second compressor (A2)
will be designated as Digital Stage 2.

On units with four Digital Scroll Compressors, there may be instances
where compressor numbers on the module do not correlate with the
mechanical compressors’ numbers. Therefore, Digital Stage 1 refers to
the fi rst set of Digital Scroll Compressors (A1/B1) that will stage on
together and Digital Stage 2 refers to the second set of Digital Scroll
Compressors (A2/B2) that will stage on together. Please refer to AAON’s
wiring diagram for specifi c wiring of the unit.

Compressor Operation (Heat/Cool)

A compressor can energize if the following is true:

1. There is 24 VAC applied to the appropriate Binary Input for

the Compressor.

2. If two compressors are enabled simultaneously, a 5 second

staging delay will occur.

3. Suction Pressure is above the Low Suction Pressure Cooling

(Heating) Setpoint.

4. Proof of Flow for the appropriate water loop is made.

5. Leaving Water Temp is above the Leaving Water Safety

Setpoint (Heating Only).

6. A minimum off time of 3 minutes is met for that compressor.

NOTE: If the WSHP-X Module receives a signal on the Heat

Enable input, it will operate using the Heating Mode
Setpoints.

Cooling Mode

NOTE: Control of digital compressor(s) is only available when

the WSHP-X Module is connected to the VCM-X WSHP
Series Controller or SA Series Controller.

Fixed Compressors Only

When a Cool Signal is received, the WSHP-X Module will go into
Cooling Mode. Once Proof of Water Flow has been made, they will
sequentially stage according to Table 1 on page 16, using Stage Up and
Stage Down delays to maintain the Supply Air Setpoint that is broadcast
from the VCM-X WSHP Series Controller or SA Series Controller.

Digital Scroll Compressor Control

When a Cool Signal is received, the WSHP-X Module will go into Cool-
ing Mode. Once Proof of Water Flow has been made and a start-up delay
has been met, Compressor A1 (and B1*) will energize and Digital Stage 1
Analog Output will go to 50% and modulate as necessary to maintain the
Supply Air Temperature at the Active Supply Air Setpoint that is broad-
cast from the VCM-X WSHP Series Controller or SA Series Controller.

When Digital Stage 1 reaches 100%, a stage up timer is started. If Digital
Stage 1 stays at 100% for the stage up timer, Compressor A2 (and B2*)
will energize and both Digital Stage 1 and Digital Stage 2 outputs will
go to 50% and will begin to modulate together.

If both systems are energized and they go below 30% and the Supply Air
is below the Supply Air Setpoint by the Cooling Stage Window value,
the stage down timer is started. If the systems remain below 30% for
the duration of the stage down timer, Digital Stage 2 will deactivate and
Digital Stage 1 will go to 60%. Digital Stage 1 will stage down if it is
at 0% for the duration of the stage down timer.

* If confi gured for 4 modulating compressors.

Heat Pump Heating Mode

Heating Mode works the same as Cooling Mode except the Reversing
Valve is switched and the sequence is opposite. Compressors modulate
up when below the Heating Supply Air Setpoint and modulate down
when above the setpoint.

Dehumidifi cation Mode

Fixed Compressors Only

In the Dehumidifi cation Mode, if this unit has only fi xed compressors,
they will sequentially stage according to Table 1 on page 16 to maintain
the Suction Pressure Setpoint. Compressors A1 & B1 will stage on to-
gether fi rst followed sequentially by A2 & then B2. Stage Up and Stage
Down delays will apply.

Digital Scroll Compressor Control

In Dehumidifi cation Mode, compressors will be controlled to maintain
the Suction Pressure Temperature Setpoint. Digital Stage 1—Compres-
sor A1 (and B1*) will modulate up to 100% before Digital Stage 2—
Compressor A2 (and B2*) can be energized. When Digital Stage 2 is
energized, Digital Stage 1 will be locked at 100%.

* If confi gured for 4 modulating compressors.

Staging Delays

Staging Delays minimum run times and minimum off times are sent from
the VCM-X WSHP Series Controller or SA Series Controller.

Revised: 12/16/13