Important Wiring Considerations

Please read carefully and apply the following information when wiring
the WSHP-X Module:

1. To operate the WSHP-X Module in Stand-Alone mode, you

must connect power to the 24 VAC input terminal block.
Do not allow wire strands to stick out and touch adjoining
terminals. This could potentially cause a short circuit.

2. The 1 to 5 VDC signals for the Compressor modulation need

to use 18-gauge shielded twisted pair cable, and the Drain wire

must be the GND signal.

3. All 24 VAC wiring must be connected so that all ground

wires remain common. Failure to follow this procedure can

result in damage to the module and connected devices.

4. Be sure all modular wiring harness connectors are seated

fi rmly in their respective modular connectors on the circuit

board.

Installation & Wiring

5. All wiring is to be in accordance with local and

national electrical codes and specifi cations.

6.

Check all wiring leads at the terminal block for tightness.
Be sure that wire strands do not stick out and touch adjacent
terminals. Confi rm that all transducers required for your
system are mounted in the appropriate location and wired into
the correct terminals.

Stand-Alone Wiring Single Water

Circuit

To operate the WSHP-X Module as Stand Alone, connect the Module to
a 24 VAC power connection with an appropriate VA rating. See Figure
3
for wiring.

Figure 3: Water Source Heat Pump X Module as Stand-Alone for Single Water Circuit

NOTE:

NORMALLY

OPEN AND RATED FOR 24 VAC POWER ONLY

ALL RELAY OUTPUTS ARE

COMPRESSOR A2 ENABLE OUTPUT

COMPRESSOR A1 ENABLE OUTPUT

GND

T1

BIN1

R

E

R1

R4
R5

R3

R2

COMM

CIRCUIT A

SUCTION PRESSURE TRANSDUCER

BK

RD

WH

BK

RD

WH

WATTMASTER CONTROLS

COMPRESSOR B1 ENABLE OUTPUT
COMPRESSOR B2 ENABLE OUTPUT

ALARM OUTPUT

BIN3

BIN5
BIN6

COM

LEAVING WATER TEMPERATURE

NOTE:
OUTPUTS ARE NOT USED ON
STAND ALONE APPLICATIONS

HVAC UNIT CONNECTIONS

CIRCUIT B

SUCTION PRESSURE TRANSDUCER

GND

24 V

A

C

- 1 AMP MAXIMUM LOAD

OE334-36-WSHPX-A

Water Source Heat Pump X

Module

BIN2

BIN4

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHPX-A WSHP-X MODULE

AAON NO.: V18330

WattMaster Label

#SW000054

Rev.: 1A

E-BUS

CONNECT

E-BUS

CONNECT

+24

V

AC

GND

www.orioncontrols.com

www.aaon.com

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

- COMP. A1 EN.

- HEAT ENABLE

- COMP. A2 EN.

- WATER POF

- COMP. B1 EN.

- WATER POF

- COMP. B2 EN.

- COMMON

T 1

T 2

GND

- LEAVING WATER TEMP A

- GROUND

- LEAVING WATER TEMP B

AO1

A2O

STAGE 1- COMP. A1/B1-

STAGE 2 - COMP. A2/B2

DIGITAL COMP. A1, A2, B1, B2

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5
RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO CNTLR C2 TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

WATER POF SYSTEM A CONTACT

COMPRESSOR A1 ENABLE CONTACT

HEAT ENABLE CONTACT

WATER POF SYSTEM B CONTACT

COMPRESSOR A2 ENABLE CONTACT

COMPRESSOR B1 ENABLE CONTACT

COMPRESSOR B2 ENABLE CONTACT

BIN7

SIG 1

GND

+V

SIG 1

GND

+V