WSHP-X Module

3

Overview

The OE334-26-WSHPX-A Water Source Heat Pump X (WSHP-X)
Module monitors the compressors on an AAON

®

Water Source Heat

Pump unit and can disable the compressors based on low Suction Pres-
sure, Leaving Water Temperature, and Water Proof of Flow inputs. It
also utilizes a Delay Timer to prevent the compressors from turning on
at the same time.

The WSHP-X Module’s water circuit confi guration can be either single
or dual. There are eight R410-A glycol confi gurations for the WSHP-X
Module—0%-40% in increments of 5%. There are two refrigerant selec-
tions—R410-A refrigerant and R-22 refrigerant. If R-22 refrigerant is
selected, the glycol will automatically default to 0%.

The WSHP-X Module can be used stand-alone. It can also be connected
to the VCM-X WSHP Controller or the SA Controller using the E-BUS
Distribution Module or the module can be directly connected to the
VCM-X WSHP E-BUS Controller or SA E-BUS Controller, allowing
the Module to receive setpoints from the Controllers. See chart on page
2
for part numbers. Please note: The SA series of controllers only work
with the R410-A dual water circuit confi gurations.

The WSHP-X Module requires a 24 VAC power connection with an
appropriate VA rating.

NOTE: The WSHP-X Module is factory set for R410-A and 0%

glycol.

Module Overview

Figure 1: Water Source Heat Pump X Module

Features

The WSHP-X Module provides the following:



Can be operated stand-alone or connected to a

VCM-X WSHP Controller or SA Controller using

the

E-BUS

Distribution Module to E-BUS interface



Can be directly connected to a VCM-X WSHP E-BUS

Controller or SA E-BUS Controller



Capable of controlling digital compressors when

connected to a VCM-X WSHP Series Controller or

SA Series Controller



Monitors suction pressure, leaving water

temperature, and water proof of fl ow



Provides Delay Timer to prevent compressors

from turning on at the same time



Contains a 2x8 LCD character display and 4 buttons

that allow for status display, setpoint changes, and

confi guration changes

NOTE: The WSHP-X Module contains no user-serviceable parts.

Contact qualifi ed technical personnel if your Module is
not operating correctly.

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHPX-A WSHP-X MODULE

AAON NO.: V18330

WattMaster Label

#SW000054

Rev.: 1A

E-BUS

CONNECT

E-BUS

CONNECT

+24

V

AC

GND

www.orioncontrols.com

www.aaon.com

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

- COMP. A1 EN.

- HEAT ENABLE

- COMP. A2 EN.

- WATER POF

- COMP. B1 EN.

- WATER POF

- COMP. B2 EN.

- COMMON

T 1

T 2

GND

- LEAVING WATER TEMP A

- GROUND

- LEAVING WATER TEMP B

AO1

A2O

STAGE 1- COMP. A1/B1-

STAGE 2 - COMP. A2/B2

DIGITAL COMP. A1, A2, B1, B2

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5
RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO CNTLR C2 TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS