Wshp-x module, Installation & wiring, Technical guide 4 – Orion System Water Source Heat Pump X Module User Manual

Page 4: Power supply, Environmental requirements, Mounting

Advertising
background image

WSHP-X Module

Technical Guide

4

Installation & Wiring

Power Supply

The WSHP-X Module requires a 24 VAC power connection with an
appropriate VA rating.

If you will be connecting the WSHP-X Module to a VCM-X WSHP
Series Controller or SA Series Controller, one of the most important
checks to make before powering up the system for the fi rst time is to
make sure that the Controller is confi gured properly for your applica-
tion. Refer to the VCM-X Controller Technical Guide, VCM-X Modular
E-BUS Controller Technical Guide,
SA Controller Technical Guide, or
SA E-BUS Controller Technical Guide
for more information.

WARNING: Observe polarity! All boards must be wired

GND-to-GND and 24 VAC-to-VAC. Failure to

observe polarity could result in damage to the

boards.

Environmental Requirements

The WSHP-X Module needs to be installed in an environment that can
maintain a temperature range between -30°F and 150°F and not exceed
90% RH levels (non-condensing).

Mounting

The WSHP-X Module is housed in a plastic enclosure. It is designed to
be mounted by using the 3 mounting holes in the enclosure base. It is
important to mount the module in a location that is free from extreme
high or low temperatures, moisture, dust, and dirt. Be careful not to
damage the electronic components when mounting the module. See
Figure 2
for Module dimensions (in inches).

Figure 2: Water Source Heat Pump X Module Dimensions

WATTMASTER CONTROLS

5.64

5.83

2.07

4.14

5.05

0.29

0.56

0.18 DIA. TYP. 3 PL.

Note: Height is 1.49 inches.

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHPX-A WSHP-X MODULE

AAON NO.: V18330

WattMaster Label

#SW000054

Rev.: 1A

E-BUS

CONNECT

E-BUS

CONNECT

+24

V

AC

GND

www.orioncontrols.com

www.aaon.com

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

- COMP. A1 EN.

- HEAT ENABLE

- COMP. A2 EN.

- WATER POF

- COMP. B1 EN.

- WATER POF

- COMP. B2 EN.

- COMMON

T 1

T 2

GND

- LEAVING WATER TEMP A

- GROUND

- LEAVING WATER TEMP B

AO1

A2O

STAGE 1- COMP. A1/B1-

STAGE 2 - COMP. A2/B2

DIGITAL COMP. A1, A2, B1, B2

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5
RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO CNTLR C2 TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS