Wshp-x module, System status a screens, Technical guide – Orion System Water Source Heat Pump X Module User Manual

Page 23: 23 system status a screens

Advertising
background image

Technical Guide

WSHP-X Module

23

System Status A Screens

Refer to the following map when navigating through the System Status
A Screens. From the SYSTEM STATUS A Screen, press

<ENTER>

to

scroll through the screens.

SYSTEM

STATUS A

A1 COMP

OFF,PENDING,ON or

Reason for Fail

H2O TEMP

NO SENSR

Status Screens shown below will scroll automatically if LCD display is

left on this screen for 20 seconds.

SYSTEM A, COMPRESSOR 1

This screen displays the current status of the A1 Compressor.

OFF

PENDING: Compressor is off, but a request is made to be on, but the

1 minimum off time has not been met.

ON: HEAT or Cool

REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow

LEAVING WATER TEMPERATURE READING

OR “NO SENSOR”

A2 COMP

OFF,PENDING,ON or

Reason for Fail

SYSTEM A, COMPRESSOR 2

This screen displays the current status of the A2 Compressor.

OFF

PENDING: Compressor is off, but a request is made to be on, but the

1 minimum off time has not been met.

ON: HEAT or Cool

REASON FOR FAILURE: Low Pres, Lockout, Low H2O, No Flow

A1 PRES

XXX

SYSTEM A, COMPRESSOR 1 PRESSURE READING

A2 PRES

XXX or NOT USED

SYSTEM A, COMPRESSOR 2 PRESSURE READING

If Single Water Confi guration, this screen will display “NOT USED.”

System Status A Screens

PO FLOW

YES or NO

PROOF OF WATER FLOW

AOUT1

X%

ANALOG OUTPUT 1 PERCENT

0 - 100%

AOUT2

X%

ANALOG OUTPUT 2 PERCENT

0 - 100%