Sequence of Operation

Stand-Alone Input Commands

Compressor On/Off

A 24 volt signal to Binary Inputs #1-4 initiates each Compressor’s On
function. The source for this signal would typically come from Y1 to
Y4 calls from the thermostat.

Heat Enable On/Off

A 24 volt signal on this input indicates the unit is in the Heating Mode.
Typically, the source for this signal is the “O” call from the thermo-
stat.

Water Proof of Flow System On/Off

A 24 volt signal to Binary Inputs #6-7 indicates Water Proof of Flow
for each system.

Suction Pressure Analog Inputs

Sensors from Analog Inputs #1-4 correlate with the Suction Pressure of
each Compressor (250 PSI).

Leaving Water Temperature Thermistor Inputs

T1 correlates with Compressors A1 & A2 (RLY1 and RLY2). T2 cor-
relates with Compressors B1 & B2 (RLY3 and RLY4).

Input Commands (VCM-X WSHP or SA

Connection)

NOTE: When the term “ON” is used, it means there is either 24

VAC on the appropriate Binary Input or a call-to-run
signal is being received from the VCM-X WSHP Series
or SA Series Controller. When the term “OFF” is used,
it means there is either 0 VAC on the appropriate Binary
Input or the call-to-run signal from the VCM-X WSHP
or SA has been removed.

Compressor On/Off

Instead of a physical input signaling the Compressor On/Off function,
the VCM-X WSHP Series Controller or SA Series Controller commu-
nications drives the Compressor On/Off function.

Heat Enable On/Off

As with the Compressor On/Off function, the VCM-X WSHP Series or
SA Series Controller communicates to the Module that it is in Heat Mode.

Table 4: Factory-Set Default Setpoints - Glycol

Glycol Default Setpoints

Description

R22

0%

Glycol

R410-A

0%

Glycol

R410-A

5%

Glycol

R410-A

10%

Glycol

R410-A

15%

Glycol

R410-A

20%

Glycol

R410-A

25%

Glycol

R410-A

30%

Glycol

R410-A

35%

Glycol

R410-A

40%

Glycol

UNSAFE
SUCTION

20 PSIG

40 PSIG

40 PSIG

40 PSIG

40 PSIG

40 PSIG

40 PSIG

40 PSIG

40 PSIG

40 PSIG

LOW SUCTION
HEAT MODE

57 PSIG

100 PSIG

93 PSIG

87 PSIG

82 PSIG

75 PSIG

65 PSIG

58 PSIG

49 PSIG

45 PSIG

LOW SUCTION
COOL MODE

57 PSIG

87 PSIG

85 PSIG

85 PSIG

85 PSIG

85 PSIG

85 PSIG

85 PSIG

85 PSIG

85 PSIG

LOW LEAVING
WATER TEMP

37ºF

37ºF

34ºF

30ºF

27ºF

20ºF

15ºF

9ºF

2ºF

0ºF