Remotec ZTS-110 V3.12 User Manual

Page 32

Advertising
background image

31

Association group_3: (Auto report)
- Association group_3 is used to report status change to gateway. (Only gateway

or controller can be assigned in this association group)
ZTS-110 will trigger AUTO report function if one of below status is changed.

I.

Operation mode (Off, Heat, Cool, Auto)

II. Operation state (Heat on or off, Cool on or off)
III. Fan mode (Auto, Auto low)
IV. Fan state (Fan on or Fan off)

o

V. Heat set point (report in precision 1 after decimal, e.g. 21.1 C )

o

VI. Cool set point (report in precision 1 after decimal, e.g. 23.3 C )

o

VII. Current room temperature (report in precision 1 after decimal, e.g. 24.0 C)

o o

(It will trigger room temperature report if there is 4 F or 2 C (default) differ from
last report. You can change this setting by set the configuration parameter)

Note: Total 5 devices (nodes) can be assigned in total 3 association groups. Below

table lists out the devices (nodes) allocations in the 3 association groups.

Important: Please do not associate heat pump and compressor devices in same
association group because heat pump and compressor device cannot be turned on
simultaneously!

Association Groups setting example (case 3):

Case No.

No. of Node ID in

Association group_1

No. of Node ID in

Association group_2

No. of Node ID in

Association group_3

Case 1

4

0

1 (AUTO report)

Case 2

3

1

1 (AUTO report)

Case 3

2

2

1 (AUTO report)

Case 4

1

3

1 (AUTO report)

Case 5

0

4

1 (AUTO report)

F-BW8041 (ZFM-80)
(Node ID-A)

F-BW8041 (ZFM-80)
(Node ID-B)

Z-Wave Gateway
(Node ID-E)

Association group_1
for Heat Pump

Association group_2
for Compressor

Association group_3
for Auto report to
gateway

F-BW8031
(ZTS-110)

F-BW8041 (ZFM-80)
(Node ID-C)

F-BW8041 (ZFM-80)
(Node ID-D)