Installation – Scotsman HID312 Service Manual User Manual

Page 11

Advertising
background image

HID312, HID525, HID540

Service Manual

April 2015

Page 11

Installation

Installation should be done by an experienced ice

machine installer. To locate one, call the number on

the back of this manual or go to Scotsman’s website

www.scotsman-ice.com to identify a local distributor or

service company.
The machine will require power, water and drain.

Locate the water supply fitting on the lower back of

the cabinet and obtain the correct fitting to connect

the water supply.
Plumbing Fittings:

• Potable water inlet: 3/8 male flare.
• Cabinet drain: 3/4 FPT.
• Water cooled condenser inlet: 3/8 FPT.
• Water cooled condenser drain: 1/2 FPT

All models:
Connect the potable water supply to the inlet

at the bottom back of the unit. 3/8” OD tubing

recommended. Water filters may be used but are not

required. Note that activated carbon or charcoal water

filters are used for taste and odor problems but also

take out any chlorine that the local water agency may

have added for purification. That can require more

frequent sanitization of the equipment.
Connect drain tubing to the central drain fitting at the

back of the cabinet. Use 3/4 inch rigid tubing, use

material to meet local codes. The drain basin in the

machine will act as an internal vent, no additional

vent should be required unless there is a very long

horizontal run. Drain tubing must pitch down 1/4 inch

per foot to the building drain. Insulation of drain tubing

is recommended for most environments.
Water cooled models:
Connect water or coolant supply (if using recirculating

system) to the condenser inlet.
Connect drain (or return if a recirculating system) to

the condenser drain. Use only rigid tubing. Do not

vent this drain tube.

Electrical Supply - 115 volt models
Plug the unit into a dedicated 15 amp outlet. The unit

must be the only device on the circuit. Confirm the

outlet is properly grounded and is in good condition.

Worn outlets should be replaced as they can cause

erratic operation of equipment. Do not use an

extension cord. Do not cut off the ground plug on the

power cord.
Ground fault outlets are not recommended. If ground

fault is required a ground fault breaker should be

used.
Use the services of a licensed electrician when

needed and conform to local and national codes.
Position the unit in its final location.
Level the unit front to back and left to right.
Seal to the countertop as required per local codes.

Drain Tubing

Potable Water

Connection

Air Cooled Utilities

Water Cooled Utilities

Condenser

Inlet

Condenser

Drain

Power

Cord

Power

Cord

Advertising
This manual is related to the following products: