Test procedures – Scotsman HID312 Service Manual User Manual

Page 28

Advertising
background image

HID312, HID525, HID540

Service Manual

April 2015

Page 28

Test Procedures

Photo-Eye Bin Control
Remove front panel.
Check controller code display. If the unit is in ice

making mode (status light on) there will normally

either be an F or a b displayed.
If the bin is full, b is displayed.
If the bin is not full and the unit is in ice making mode,

F is displayed.
if the bin is not full and the unit is off, O is displayed.
False bin full: If the bin is not full and b is displayed:
1. Check for loose connection at the harness to the

photo eye sensors.

2. Check for broken wire at sensor.
3. Check for something blocking the sensors, which

can include scale buildup.

Rotation Sensor
The sensor consists of a pick up and a magnet. The

pick up has a wire that connects to the controller. The

magnet is in the rotating magnet holder on top of the

auger motor. if the rotor is loose, it will not rotate and

the sensor will shut the machine off for no rotation.
1. Remove front and left side panels.
2. Remove motor cover.
3. Check that rotor has magnet and is secure to

motor shaft.

Note: Special thin open end wrench may be needed

to hold motor shaft, it fits under the magnet rotor.
Dispensing Motor
See chart on prior page.
Remove splash panel.
Place voltmeter probes on motor terminals.
Press Dispense Ice and confirm voltage. If voltage is correct and motor does not function, replace dispense

motor.
Note: 230 volt motor in an 115 volt machine will rotate with an empty bin but not one with ice. Be SURE to

confirm voltage on label to match ice machine voltage.

Magnet

Rotor