Test procedures - refrigeration – Scotsman HID312 Service Manual User Manual

Page 29

Advertising
background image

HID312, HID525, HID540

Service Manual

April 2015

Page 29

Test Procedures - Refrigeration

The HID refrigeration system is steady-state. When

in operation and stabilized, it will maintain nearly

constant discharge and suction pressures.
Items that can affect that are:
• Irregular water flow
• Erratic thermostatic expansion valve
• Changes in room air temperature
Normally use of refrigeration gauges is unnecessary.

If the unit is making ice properly, it is highly likely that

all is normal. Refrain from attaching gauges, and

then only use very short hoses to avoid changing

the amount of refrigerant charge. See pressure

information on page 9.
The compressor gets its power from the contactor,

which is operated by the controller. It must be working

or the compressor will be off.
Compressor Starting
The HID312 uses a current relay for starting. The

HID525 and HID540 use a potential relay. Both have

start capacitors.
HID312 current relay: The contacts of a current relay

are normally open and close when the current is high.

They stay closed until the compressor starts and the

current drops off.
Compressor starts but current too high, overheats. If

the relay does not open the start winding will remain

powered and there will be current in the wire between

the start capacitor and the compressor. Replace the

relay.
Compressor does not start. Current relay contacts

may be open because relay coil is open, check for

continuity. Start capacitor may have failed.
HID525 or HID540 potential relay: The contacts of

this relay are normally closed and open when the

compressor starts.
Compressor starts but current too high, overheats. If

the relay contacts do not open, there will be current

from the start capacitor. Replace the relay.
Compressor does not start. Relay contacts open,

check for continuity. Replace relay if open. Start

capacitor may have failed.

Capacitor Testing
Capacitors may be tested using a multimeter, but

begin with a visual test. A good indication of a failed

capacitor is one that is bulging or leaking.
If the capacitor looks ok, check it with a multimeter.
1. Discharge the capacitor.
2. Set a digital meter to a high resistance scale of at

least 4k.

3. Put the probes on the capacitor terminals and

observe the display. It should provide a reading

and then show Open Line. If no reading, the

capacitor has failed and should be replaced.

If the meter has a Capacitance setting, use it to

measure the capacitance, replace if not near to the

mfd listed on it.
Compressor Testing
Because the compressor is the hermetic type, the

available testing methods are limited. Some items that

can be measured are winding resistance and amp

draw.
If the compressor does not start and a check with an

amp meter shows it does not draw any current, it is

likely it has an open winding or overload. Those can

be checked using a multimeter.
If the compressor is hot the overload may be open. An

open overload is an indication of a worn compressor,

defective starting components or high superheat.
Note: Normal operating temperature of the

compressor dome is 85 - 95 degrees F. - warm to the

touch.
If the overload is open and the compressor is not hot,

the overload itself could be the problem. Overloads

also open due to high current and a shorted winding

could cause that. Check for shorted or grounded

windings with a multimeter.
High superheat is caused by lack of refrigeration,

possibly from low charge or a TXV starving the

evaporator.

Advertising
This manual is related to the following products: