INSTALLATION

Continued

CAUTION: Use only new,

black iron or steel pipe. Inter-

nally-tinned copper tubing may

be used in certain areas. Check

your local codes. Use pipe of

1/2" or greater diameter to allow

proper gas volume to fireplace.

If pipe is too small, undue loss

of volume will occur.

Installation must include an equipment shutoff

valve, union and plugged 1/8" NPT tap. Locate

NPT tap within reach for test gauge hook up.

NPT tap must be upstream from heater (see

Figure 22).
IMPORTANT:

Install equipment shutoff valve

in an accessible location. The equipment shutoff

valve is for turning on or shutting off the gas to

the appliance.
Check your building codes for any special re-

quirements for locating equipment shutoff valve

to fireplaces.
Apply pipe joint sealant lightly to male NPT

threads. This will prevent excess sealant from

going into pipe. Excess sealant in pipe could result

in clogged fireplace valves.

WARNING: Use pipe joint

sealant that is resistant to liquid

petroleum (LP) gas.

We recommend that you install a sediment trap in

supply line as shown in Figure 22. Locate sediment

trap where it is within reach for cleaning. Install

in piping system between fuel supply and heater.

Locate sediment trap where trapped matter is not

likely to freeze. A sediment trap traps moisture

and contaminants. This keeps them from going

into fireplace controls. If sediment trap is not

installed or is installed wrong, fireplace may not

run properly.

Propane/LP
Supply Tank

External Regulator

Figure 21 - External Regulator With Vent

Pointing Down

Vent Pointing Down

* Purchase the optional CSA design-certified

equipment shutoff valve from your dealer. See

Accessories,

page 40.

Figure 22 - Gas Connection

CSA Design-
Certified Equipment
Shutoff Valve With
1/8" NPT Tap*

3" Minimum

Approved
Flexible Gas
Line

Pipe Nipple Cap Tee Joint

Propane/LP
From External
Regulator (11"
W.C.** to 14"
W.C. Pressure)

NATURAL
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)

Sediment Trap