7.2 Configuration by terminal
ED-10 TCP internal commands must be used to configure by terminal program.

TYPE command
Configuration parameter values can be read by using the 'type' command. E.g. 'type
chip.set

', will list the chip.set file.

The 'type' command will list configuration parameters and their values, regardless of the
ED-10 TCP operating mode.
The parameters/values are stored in two pairs of configuration files; chip.set,-ini,
factory.set, -ini. See chapter 6.3.
Values used at reboot are stored in the chip.set, -ini files.
Please note, the configuration files also contain parameters that can not be changed.

COPY and REBOOT commands
The 'copy' and 'reboot' commands are used to change ED-10 TCP working mode. The
contents in ED-10 TCP internal file 'autoexec.bat' decides the mode ED-10 TCP will
enter after a reboot.
The 'copy' command is used to copy the ED-10 TCP internal files 'app.bat' or 'config.bat'
to 'autoexec.bat', e.g. 'copy config.bat autoexec.bat

'.

Reboot is achieved by either the 'reboot' command or by switching the power off and on.

EXIT command
To change configuration parameter values the ED-10 TCP must be in config mode.
When in config mode a value change is requested by a [parameter] [value] pair input,
e.g. 'datarate 19 200

'.

When all requested changes have been input the 'exit' command must be used to store
the changes into the configuration files. The 'exit' command also copies app.bat to
autoexec.bat ensuring application mode is entered when ED-10 TCP is rebooted.