Specification – Westermo ED-10 TCP User Manual

Page 6

Advertising
background image

6

6609-2211

3. Specification

Network Interface

10BASE-T. IEEE std 802.3, 2000 Edition.

Data rate

10 Mbit/s, half duplex.

Mechanical

RJ-45 Modular Jack (ISO/IEC 8877:1992),
Unshielded or shielded (UTP/STP).

Serial Interface 1

RS-232 or RS-422/485

Data rate

300–115 200 bit/s Full, half duplex or simplex.

Data format

7–8 Data Bits, Odd, Even or None Parity Bit,
1–2 Stop Bits (2 stop bits when no parity only)

Control signals*

RTS, CTS, DSR, DCD, DTR

Termination**

Termination and fail safe, on or off

Mechanical

RS-232: 9-pin female D-sub.
RS-422/485: Screw Terminal.

Serial Interface 2

RS-232 (used for local configuration only)

Data rate

19 200 Bit/s

Data format

8 Data Bits, No Parity Bit, 1 Stop Bit

Mechanical

9-pin female D-sub.

Power Interface

Rated voltage

10–60 V DC, polarity independent / 12–30 V AC.

Rated current

350 mA, max @ 10 V DC input.

Rated frequency

48–62 Hz

Mechanical

Screw Terminal.

Isolation***

Functional and safety

Power Interface to
all other Interfaces

4.2 kV DC, 3 kV RMS @ 50 Hz.

Network Interface
to serial interface

2.1 kV DC, 1.5 kV RMS @ 50 Hz.

Enhanced Transient/Surge Protection

Power Interface

±4 kV, EN 61 000-4-5:1995 Class 4

Network Interface

±2 kV, EN 61 000-4-5:1995 Class 3

Serial Interface**

±2 kV, EN 61 000-4-5:1995 Class 3

Serial Interface*

±0.5 kV, EN 61 000-4-5:1995 Class 1

Application

Latency (minimum)

Serial to Network: 4 ms
Network to Serial: 10 ms

Throughput (maximum)

115 kbit/s (1.44 MB data)

Network protocols

TCP, IP, ARP, ICMP (Ping), Telnet

*

RS-232 only.

** RS-422/485 only.
*** Test voltage applied for 60 sec.

Advertising