33

• Connect the master to the terminals

Main Cluster Master as follows:

– Connect the line conductor to the

terminal 1 :L1.

– Connect the neutral conductor to the

terminal 2 :N.

– Connect the grounding conductor to the

terminal 3 :PE.

5. Connect the Sunny Island inverters of the extension cluster as described under point 4. Begin

with slave 2 of extension cluster 1 and observe the labels on the terminals.

6. Bundle the connection cables with cable ties above the double-membrane seal. This helps

relieve tension at the terminals.

7. Reinsert the cover of the Sunny Island connection area.
8. Insert the four screws into the cover of the Sunny Island connection area and fasten them

hand-tight.

7.9 Grounding the Multicluster System

The neutral conductors inside the Multicluster Box are not connected to the grounding conductor by
default. To ensure safe operation of the multicluster system, the following measures must be taken prior
to commissioning:

Cable requirements:

☐ Conductor material: copper
☐ Maximum conductor cross-section: 300 mm²

Procedure:

• Ground the multicluster system outside the Multicluster Box on either the generator side or the

load side. Connect the neutral conductor to the grounding conductor, observing all standards
and directives applicable at the installation site.