12  Technical Data

Operating Manual

MC_BOX_36-BE-en-20

41

12 Technical Data

Load Connection

Sunny Island Connection

Number

1 x three-phase

Rated power

300 kW

Rated grid voltage between L and N

230 V

Rated grid voltage between L1 and L2

400 V

AC voltage range between L1 and N

172.5 V to 250 V

AC voltage range between L1 and L2

300 V to 433 V

Rated frequency

50 Hz

Frequency range

40 Hz to 70 Hz

Current at rated values

3 x 435 A

Diameter of the screws for cable connection

12 mm

Torque

25 Nm

Maximum connectable conductor cross-section

300 mm²

Fuse

LV/HRC size 3

Permissible fuse rating

100 A to 500 A

Maximum number of Sunny Island inverters

36

Rated power Sunny Island

216 kW

Current at Sunny Island ratings

3 x 313 A

Sunny Island power at 45°C

195 kW

Sunny Island current at 45°C

3 x 283 A

Sunny Island power over 30 minutes at 25°C

288 kW

Sunny Island current over 30 minutes at 25°C

3 x 417 A

Conductor cross-section

6 mm² to 16 mm²

Fuses

36 x circuit breaker C40 A