12 Technical Data
SMA Solar Technology AG
42
MC_BOX_36-BE-en-20
Operating Manual
Generator Connection
PV Plant Connection
Ground Connection
Number
1 x three-phase
Rated grid input power
300 kW
AC input current
3 x 435 A
Maximum relative short-circuit current
10 kA
Diameter of the screws for cable connection
12 mm
Torque
25 Nm
Maximum connectable conductor cross-section
300 mm²
Fuse
LV/HRC size 3
Permissible fuse rating
100 A to 500 A
Number
1 x three-phase
PV rated power
360 kW
AC current at rated values
3 x 522 A
Maximum relative short-circuit current
10 kA
Diameter of the screws for cable connection
12 mm
Torque
25 Nm
Maximum connectable conductor cross-section
300 mm²
Fuses
None
Diameter of screws on grounding busbar
12 mm
Maximum torque
25 Nm
Maximum connectable conductor cross-section
300 mm²