10 maintenance – SMA MULTICLUSTER BOX 36 User Manual

Page 38

Advertising
background image

10  Maintenance

SMA Solar Technology AG

38

MC_BOX_36-BE-en-20

Operating Manual

10 Maintenance

The Multicluster Box must be serviced at regular intervals. Note that the maintenance interval is
influenced by the mounting location and the ambient conditions. The Multicluster Box must be
serviced more frequently if it is installed in environments with severe dust pollution.

Danger to life due to electric shock
High voltages are present in the Multicluster Box and the multicluster system. Touching live
components results in death or serious injury due to electric shock.

• Disconnect the multicluster system from all voltage sources before carrying out any work on

the Multicluster Box (see Section 9, page 37).

Risk of burns
Busbars and terminals in the Multicluster Box can get hot during operation.

• Do not touch busbars or terminals.

Maintenance work

Recommended
maintenance
interval

Check the inside of the Multicluster Box for dirt, moisture and water
ingress.

• If necessary, clean the Multicluster Box and take appropriate

actions.

12 months

Check stability of all connections. Disconnect the Multicluster Box from all
voltage sources (see Section 9, page 37).

• Tighten connections if necessary (for torques: see Section 12,

page 41).

12 months

Check insulation, terminals and fuse elements for any discoloration or
visible changes.

• If a customer-supplied cable, such as the load cable to the

Multicluster Box, shows discoloration or visible changes, replace it.
Disconnect the Multicluster Box from all voltage sources (see
Section 9, page 37).

• If any internal wiring or a fuse element is discolored or shows visible

changes, inform the SMA Service Line.

12 months