Troubleshooting

Installation Manual

SB33-38-11-IA-en-62

53

Imax / overcurrent

Overcurrent on the AC side. This message is displayed if the current in the
AC grid is higher than specified.
Corrective measures

• Check the plant design and grid conditions.

K1-Close
K1-Open

Error during relay test.

Corrective measures

• If this fault frequently occurs or occurs several times consecutively,

contact the SMA Service Line.

MSD-Fac

Internal measurement comparison fault or hardware defect.
Corrective measures

• If this fault occurs frequently, contact the SMA Service Line.

MSD-Vac

Internal measurement comparison fault or hardware defect.
Corrective measures

• If this fault occurs frequently, contact the SMA Service Line.

MSD-Timeout

Internal measurement comparison fault or hardware defect.
Corrective measures

• If this fault occurs frequently, contact the SMA Service Line.

MSD-Zac

Internal measurement comparison fault or hardware defect.
Corrective measures

• If this fault occurs frequently, contact the SMA Service Line.

OFFSET

The "Offset" operating state is a normal operating state that occurs prior
to grid monitoring.
If "Offset" is displayed as an error, there is a fault in the data logging.
Corrective measures

• If this fault occurs frequently, contact the SMA Service Line.

Riso

The electrical insulation between the PV plant and ground is defective.
The resistance between the DC plus and/or DC minus connection and
ground is outside the defined limit range.
Corrective measures

• Check the insulation of the PV plant.
• Check the plant for ground faults as described in section

9.3.1 "Checking the PV Array for Ground Faults" (page 56).

ROM

The inverter's firmware is faulty.
Corrective measures

• If this fault occurs frequently, contact the SMA Service Line.

Message

Description and corrective measure