Troubleshooting

Installation Manual

SB33-38-11-IA-en-62

57

4. Measure the voltages between the positive and

negative poles of each string.

☑ A ground fault exists if the measured voltages are stable and the sum of the voltages from

the positive pole to the ground potential and from the negative pole to the ground potential
of a string is approximately equal to the voltage between the positive and negative poles.

Result

Measure

☑ You have found a ground fault.

• The installer of the PV array must remedy

the ground fault in the affected string.
You can determine the location of the
ground fault as described below.

• Do not reconnect the faulty string.
• Commission the inverter as described in

section 6.1 "Commissioning the Inverter"
(page 39).

☑ You have found no ground fault.

It is likely that one of the thermally monitored
varistors is defective.

• Check the varistors as described in section

9.3.2 "Checking the Function of the
Varistors" (page 58).