Decommissioning

SMA Solar Technology AG

62

SB33-38-11-IA-en-62

Installation Manual

7. If a communication cable is available:

– Open the inverter as described in section 7.2 "Opening the Inverter" (page 41).
– Remove the communication cable from the inverter.
– Close the inverter as described in section 7.3 "Closing the Inverter" (page 43).

8. If present, plug in the Electronic Solar Switch.

CAUTION!
Risk of burns due to hot enclosure parts

The inverter's enclosure can become hot during operation.

• Wait until the enclosure has cooled down.

NOTICE!
Damage to the inverter due to moisture and dust intrusion

If the Electronic Solar Switch is not plugged in or incorrectly plugged in during operation,
moisture and dust can penetrate the inverter.
If the Electronic Solar Switch is not correctly plugged in, this can cause contacts to wear in
the Electronic Solar Switch or the Electronic Solar Switch might fall down. This can result in
yield loss and damage to the Electronic Solar Switch.
Always plug in the Electronic Solar Switch as described in the following:

• Do not tighten the screw in the Electronic Solar Switch.
• Firmly plug in the Electronic Solar Switch until it is flush with the enclosure.
• Ensure that the maximum distance between the Electronic Solar Switch and the

enclosure is 1 mm.